Synchronous transfer function is used to realize smooth switch between VFD and grid,
avoid electric shock to the electrical net, and prolong electrical
equipment’s working life.
4-6 Multi Motors Parameters Storage
Table 4-73 Storage region of multi motors
No.
Parameter number
Motor 1
P2001--P2300
Motor 2
P2301--P2600
Motor 3
P2601--P2900
Motor 4
P2901
—P3200
Motor 5
P3201
—P3500
Motor 6
P3501
—P3800
Motor 7
P3801
—P4100
Motor 8
P4101
—P4400
VFD can provide parameter storage of eight motors. The function numbers above show
the storage region of eight motors respectively.
Table 4-74 Parameters of 1
st
motor
ID
Parameter
Min
Max
Unit
Default
Description
P2003 Motor1 rated voltage
0
65535
V
6000
P2004 Motor1 rated speed
0
65535
rpm
993
P2005 Motor1 rated current
0
65535
A
74
P2006 Motor1 pole number
2
65535
6
P2007
Motor1 rated
frequency
0
65535
0.01Hz
5000
P2008 Motor1 rated torque
0
65535
10N.m
657
P2011
Motor1 stator
resistance
0
65535
mΩ
702
P2019
Motor1 flux
reference
0
65535
0.001
wb
15200
P2021
Motor1 coefficient of
SVC speed
controller Kp
0
65535
%
100
P2022
Motor1 coefficient of
SVC speed
controller Ki
0
65535
%
100
P2023
Motor1 coefficient of
SLVC speed
controller Kp
0
65535
%
33
P2024
Motor1 coefficient of
SLVC speed
controller Ki
0
65535
%
33
P2025
Motor1 coefficient of
flux controller Kp
0
65535
%
100
Содержание MVF2000 Series
Страница 2: ......
Страница 15: ...11 Standard No Standard Name Used With Adjustable Voltage or Adjustable Frequency Controls or Both...
Страница 36: ...Fig 3 15 date time adjust interface HMI System Click HMI System button to enter into HMI System...
Страница 128: ...Annex B MVF2000 Electrical parameters and dimensions table MVF2000 outline drawings shown below w D H...