Table 4-44 Current sampling fault
ID
Parameter
Min
Max
Unit
Default
Description
P465
Time duration for
current sampling
anomaly
0
65535
ms
5
P1143
Fault action
configuration: Output
Current Sampling
Fault
0
8
2
P1257
Fault duration time:
Input Current
Sampling Fault
0
65535
ms
0
P1265
Fault duration time:
Output Current
Sampling Fault
0
65535
ms
0
Table 4-45 Power cell protection
ID
Parameter
Min
Max
Unit
Default
Description
P0212
Power cell non cycle
overload: ratio
100
120
%
120
P0213
Power cell non cycle
overload: time
0
120
s
60
P1145
Fault action
configuration: Power
Cell Overload
0
8
0
P1167
Power cell fault
action configuration:
Over Temperature
0
8
6
P1168
Power cell fault
action configuration:
IGBT Driver Fault
0
8
5
P1169
Power cell fault
action configuration:
Input Phase Loss
0
8
6
P1170
Power cell fault
action configuration:
Downstream Fiber
Communication
Fault
0
8
6
P1171
Power cell fault
action configuration:
DC Bus Over
Voltage
0
8
7
Содержание MVF2000 Series
Страница 2: ......
Страница 15: ...11 Standard No Standard Name Used With Adjustable Voltage or Adjustable Frequency Controls or Both...
Страница 36: ...Fig 3 15 date time adjust interface HMI System Click HMI System button to enter into HMI System...
Страница 128: ...Annex B MVF2000 Electrical parameters and dimensions table MVF2000 outline drawings shown below w D H...
Страница 131: ...127 Fig 2 Front view Fig 3 Inside view...