Annex D
MODBUS Communication
1. Communication protocol
Communication port
:
RS485
Communication protocol
:
Modbus RTU
Communication station
:
2
Communication data structure
9600 (Baud rate), 8 (data bit), Even (Odd-even check bit) 1 (initial bit), 1 (stop bit)
2. Communication command code
Command
code
Meaning
Operable device
01
Read node state
(cannot read input node state)
S, Y, M, T, C
02
Read node state
(can read input node state)
S, X, Y, M,T, C
03
Read the content value in register
T, C, D
05
Force single node state
S, Y, M, T, C
06
Preset the value of single register
T, C, D
15
Force multiple node states
S, Y, M, T, C
16
Preset the value of multiple
registers
T, C, D
3. MODBUS Addresses of Various Parameters
No.
Type
Variable name
Register
address
MODBUS
address
R/W
Attribute
Remarks
1
Operation
parameters
Input voltage
D26001
426002
R
Measured value *1
2
Output voltage
D26002
426003
R
Measured value *1
3
Input current
D26003
426004
R
Measured value *1
4
Output current
D26004
426005
R
Measured value *1
5
Input power
D26005
426006
R
Measured value *1
6
Reference Speed
D26006
426007
R
Measured value *1
7
Actual operation
Speed
D26007
426008
R
Measured value *1
8
Reference
D26008
426009
R
Measured value
Содержание MVF2000 Series
Страница 2: ......
Страница 15: ...11 Standard No Standard Name Used With Adjustable Voltage or Adjustable Frequency Controls or Both...
Страница 36: ...Fig 3 15 date time adjust interface HMI System Click HMI System button to enter into HMI System...
Страница 128: ...Annex B MVF2000 Electrical parameters and dimensions table MVF2000 outline drawings shown below w D H...
Страница 131: ...127 Fig 2 Front view Fig 3 Inside view...