59
Bandwidth 1
Bandwidth 2
Bandwidth 3
Output
frequency
Frequency
skip point 1
Frequency
skip point 2
Frequency
skip point 3
Reference
frequency
Fig. 4-3 Frequency skipping
Table 4-55 Multi-point V/F
ID
Parameter
Min
Max
Unit
Default
Description
P0089
Multi-point V/F
enable
0
1
0
0-Disable
1-Enable
P0150
Frequency point 1 of
multi-point V/F
0
33000
0.01Hz
1000
P0151
Voltage point 1 of
multi-point V/F
0
65535
V
1600
P0152
Frequency point 2 of
multi-point V/F
0
33000
0.01Hz
3000
P0153
Voltage point 2 of
multi-point V/F
0
65535
V
5000
For the multi-point V/F function, there are 2 V/F points can be configured, and two
parameters should be set to each V/F point, namely frequency point and voltage point,
as shown in Fig. 4-4.
Voltage point 1
Output line
voltage(rms)
Frequency
point 1
Frequency
point 2
Rated
frequency
Output
frequency
Voltage point 2
Rated voltage
Fig. 4-4 Multi-point V/F