69
While the grid falls below threshold of input power loss, the DC link voltage can be
stabilized by regenerating power from motor side. If grid voltage recovers in duration
time of low voltage ride through, DC link voltage is above DC voltage lower limit of low
voltage ride through, and motor speed is above speed lower limit of low voltage ride
through, torque current will be increased and drive speed will return to its previous value.
If ride through control is chosen, there is large excitation inrush current in the input side
when grid voltage recovers. The power supply must have sufficient capacity to provide
such huge instantaneous current. So VFD will not equip with startup cabinet when ride
through control is chosen. When ride through control is disable, once loss of power is
detected, startup cabinet will trip if the startup cabinet is available.
Table 4-71 Automatic restart
ID
Parameter
Min
Max
Unit
Default
Description
P1352
Automatic restart
enable
0
1
0
0-Disable
1-Enable
P1353
Reset waiting time of
automatic restart
0
65535
0.1s
5
P1354
Trial time of
automatic restart
0
65535
0.1s
600
P1355
Number of trials for
automatic restart
1
10
4
P1356
Result of automatic
restart
-
-
-
0
0-None
1~7-
Reason for
automatic restart
failure
99-Automatic restart
succeeded
P1357
Input under voltage
automatic restart
0
1
0
0-Disable
1-Enable
P1358
Input power loss
automatic restart
0
1
0
0-Disable
1-Enable
P1359
Output over current
automatic restart
0
1
0
0-Disable
1-Enable
P1360
Output under load
automatic restart
0
1
0
0-Disable
1-Enable
P1361
Speed setting analog
loss automatic
restart
0
1
0
0-Disable
1-Enable
P1362
Transformer
temperature sensor
loss automatic
restart
0
1
0
0-Disable
1-Enable
When a fault appears, MVD stop output and alarm, as shown in Fig. 4-8. The fault is
reset a
utomatically after fault disappears and a delay period defined by P1353 “Reset
waiting time of automatic restart”. When the fault is reset, the trial time starts to count,
and drive is started automatically by flying start.
Содержание MVF2000 Series
Страница 2: ......
Страница 15: ...11 Standard No Standard Name Used With Adjustable Voltage or Adjustable Frequency Controls or Both...
Страница 36: ...Fig 3 15 date time adjust interface HMI System Click HMI System button to enter into HMI System...
Страница 128: ...Annex B MVF2000 Electrical parameters and dimensions table MVF2000 outline drawings shown below w D H...
Страница 131: ...127 Fig 2 Front view Fig 3 Inside view...