Table 4-56 Torque boost
ID
Parameter
Min
Max
Unit
Default
Description
P0004
Torque boost
voltage
0
300
‰
0
Torque boost is used to increase the output voltage during low-frequency operation and
improve the low-frequency torque characteristics of V/F control.
The setting range of the torque boost voltage is 0~300
‰. When the set value is 0, there
is no increase, but when the set value is 300
‰, the increase range is maximum.
Torque boost
voltage(%)
Output
voltage
Rated
frequency
Output
frequency
100% rated
voltage
Fig. 4-5 Torque boost
Table 4-57 AVR
ID
Parameter
Min
Max
Unit
Default
Description
P0031 AVR enable
0
1
0
0-Disable
1-Enable
P0953
Filter bandwidth of
power cell DC
voltage
0
65535
0.01Hz
20
AVR function refers to the automatic adjusting function of the output voltage: when the
AVR function is disabled, the output voltage will change with the change of the input
voltage (or the DC bus voltage); when the AVR function is enabled, the output voltage
will not change with the change of the input voltage (or the DC bus voltage), and the
output voltage will basically keep constant within the normal input voltage variation
range.
Table 4-58 Dead-band compensation
ID
Parameter
Min
Max
Unit
Default
Description
P0960
Dead-band
compensation
enable
0
1
0
0-Disable
1-Enable
Содержание MVF2000 Series
Страница 2: ......
Страница 15: ...11 Standard No Standard Name Used With Adjustable Voltage or Adjustable Frequency Controls or Both...
Страница 36: ...Fig 3 15 date time adjust interface HMI System Click HMI System button to enter into HMI System...
Страница 128: ...Annex B MVF2000 Electrical parameters and dimensions table MVF2000 outline drawings shown below w D H...
Страница 131: ...127 Fig 2 Front view Fig 3 Inside view...