V110120E
iBoot-G2+
Page 18
Action: select from
None
Heartbeat not used
Power On – Latch
Upon triggering, iBoot-G2+ will power on and remain so until changed via the
web, ibootctl.exe or direct messaging.
Power On – Follow
Upon triggering, iBoot-G2+ will power on. When the heartbeat returns,
iBoot-G2+will power off.
Power Off – Latch
Upon triggering, iBoot-G2+ will power off and remain so until changed via the
web, ibootctl.exe or direct messaging.
Power Off – Follow
Upon triggering, iBoot-G2+ will power off. When the heartbeat response
returns, iBoot-G2+ will power on.
Power Cycle
Upon triggering, iBoot-G2+ will cycle the power. iBoot-G2+ will wait the
Heartbeat Frequency x Fail Count; if the heartbeat does not return, the
power will be recycled again. This will continue until the heartbeat returns or
Heartbeat is turned off. Make sure your Heartbeat frequency is longer than
the time required to reboot your device.
Power Cycle Once
Upon triggering, iBoot-G2+ will cycle power one time. It will not cycle again
automatically until the heartbeat returns and is lost again.
Outlet: Select Main for the internal power outlet, or Exp1, Exp 2 for either of the two expansion ports.
7.8.
Using Heartbeat Monitor
With Heartbeat operational, the main iBoot-G2+ page will display the current status of this feature. The status
will be OK to indicate that iBoot-G2+ is receiving heartbeats, or that the fail counter has not yet been
exceeded.
If the fail count has been exceeded, the status will change to Triggered. The Trigger Counter indicates the
number of times the Heartbeat feature has been triggered. A counter reset button is provided when logging in
with the System password.
7.9.
Using the Heartbeat Program
The heartbeat program and instructions are available at
http://dataprobe.com/support/iboot.html