V110120E
iBoot-G2+
Page 16
Action: Select from
None
AutoPing not used
Power On – Latch
Upon triggering, iBoot-G2+ will power on and remain so until changed via the
web, telnet, DxP, etc.
Power On – Follow
Upon triggering, iBoot-G2+ will power on. When the ping response returns,
iBoot-G2+ will power off.
Power Off – Latch
Upon triggering, iBoot-G2+ will power off and remain so until changed via the
web, telnet, DxP, etc.
Power Off – Follow
Upon triggering, iBoot-G2+ will power off. When the ping response returns,
iBoot-G2+ will power on.
Power Cycle
Upon triggering, iBoot-G2+ will cycle the power. iBoot-G2+ will wait the Ping
Frequency x Fail Count; if the response does not return, the power will be
recycled again. This will continue until the ping response returns or Auto
Ping is turned off. Make sure your Auto Ping frequency is longer than the
time required to reboot your device.
Power Cycle Once
Upon triggering, iBoot-G2+ will cycle power one time. It will not cycle again
automatically until the ping response returns and is lost again.
With AutoPing operational, the main iBoot-G2+ page will display the current status of this feature. The status
will be OK to indicate that iBoot-G2+ is receiving responses to the ping, or that the fail counter has not yet
been exceeded.
If the fail count has been exceeded, the status will change to FAIL. The Fail Counter will indicate the number of
times the failure has occurred, and the Trigger Counter indicates the number of times the AutoPing action has
been triggered. A counter reset button is provided when logging in with the Admin password.
Note: All of the AutoPing Settings require a reboot of the iBoot-G2+, after clicking Save. A Reboot button will
appear at the bottom of the page. The new settings will not take effect until the unit is rebooted.
Reboot will not affect the power position of the iBoot-G2+. Upon Clicking Reboot, the Goodbye page
is displayed with a link to re-login.