19-PIN CONNECTOR ELECTRICAL CONNECTIONS
69
5
5.5 ID-NET™ INTERFACE
Pin Name
Function
R ID+
ID-NET™ n
P ID-
ID-NET™ network -
L GND
Ground
5.5.1 ID-NET™ Cables
The following instructions are referred to Figure 83, Figure 84 and Figure 85.
The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted
pair, shielded cable AWG 24 (or AWG 22) stranded flexible.
We recommend using DeviceNet cables (drop or trunk type) to the following reference
standards:
AN50325 – IEC 62026
UL STYLE 2502 80°C 30V
Cable Shield MUST be connected to earth ground ONLY at the Master.
NEVER use ID-NET™ cable shield as common reference.
The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table
below).
For Common Power Connections use only 2 wires (R and P).
-
DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do
not put it together with AC cable):
-
Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8
Volts.
-
Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide
loops between them).
Reader's chassis may be connected to earth.
Network inside the same building.
Baudrate Table
Baud Rate
125 kbps
250 kbps
500 kbps
1Mbps
Cable Length
1200 m
900 m
700 m
*
* Application dependent, contact your Datalogic Automation representative for details.
NOTE
The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates
allow longer cable lengths. The baudrate is software configurable by
authorized Datalogic Automation personnel only.
Содержание Matrix 400
Страница 1: ...MATRIX 400 Reference Manual...
Страница 59: ...CBX ELECTRICAL CONNECTIONS 49 4 Figure 55 Matrix 400 Multidrop Connection to a Multiplexer...
Страница 62: ...MATRIX 400 REFERENCE MANUAL 52 4 Figure 57 ID NET Network Connections with isolated power blocks...
Страница 63: ...CBX ELECTRICAL CONNECTIONS 53 4 Figure 58 ID NET Network Connections with Common Power Branch Network...
Страница 64: ...MATRIX 400 REFERENCE MANUAL 54 4 Figure 59 ID NET Network Connections with Common Power Star Network...
Страница 81: ...19 PIN CONNECTOR ELECTRICAL CONNECTIONS 71 5 Figure 83 ID NET Network Connections with isolated power blocks...
Страница 82: ...MATRIX 400 REFERENCE MANUAL 72 5 Figure 84 ID NET Network Connections with Common Power Branch Network...
Страница 115: ...SOFTWARE CONFIGURATION 105 8 Figure 116 Options Communication Serial Port Figure 117 Options Communication Ethernet...
Страница 142: ...www automation datalogic com...