10 TROUBLESHOOTING
10.1 GENERAL GUIDELINES
When wiring the device, pay careful attention to the signal name (acronym) on the
CBX100/500 spring clamp connectors (chp. 4). If you are connecting directly to the
Matrix 400™ M16 19-pin connector pay attention to the pin number of the signals (chp. 5).
If you need information about a certain reader parameter you can refer to the VisiSet
program help files. Either connect the device and select the parameter you’re interested in
by pressing the F1 key, or select
Help>Paramters Help
from the command menu.
If you’re unable to fix the problem and you’re going to contact your local Datalogic office or
Datalogic Partner or ARC, we suggest providing (if possible): Application Program version,
Parameter Configuration file, Serial Number and Order Number of your reader. You can
get this information while VisiSet™ is connected to the reader: the Application Program
version is shown in the Terminal Window; the Parameter Configuration can be saved to an
.ini file applying the
File>Save Configuration File
command in the Parameter Setup
window; Serial Number and Order Number can be obtained by applying the respective
command in the
Tools
menu.
TROUBLESHOOTING GUIDE
Problem Suggestion
Power ON:
the “POWER” LED is not lit.
Is power connected?
If using a power adapter (like PG6000), is it connected
to wall outlet?
If using rail power, does rail have power?
If using CBX, does it have power (check switch and
LED)?
Check if you are referring to the M16 19-pin connector
or to the CBX spring clamp connectors.
Measure Voltage either at pin
A
and pin
L
(for 19-pin
connector) or at spring clamp
Vdc
and
GND
(for CBX).
One Shot or Phase Mode
using the Input 1 (External
Trigger) or Input 2:
the ”TRIGGER” LED is not
blinking while the External
Trigger is switching.
Check if you are referring to the 19-pin connector or to
the CBX spring clamp connectors.
Is the sensor connected to the Input 1 or Input 2?
Is power supplied to the photo sensor?
For NPN configuration, is power supplied to one of the
two I1 or I2 signals (A or B)?
For PNP configuration, is one of the two I1 or I2 signals
grounded (A or B)?
Are the photo sensor LEDS (if any) working correctly?
Is the sensor/reflector system aligned (if present)?
In the Digital I/O folder check the EXTERNAL
TRIGGER or INPUT 2\
Debounce Filter
parameter
setting.
In the Operating Mode folder check the settings for
Reading Phase-ON, Acquisition Trigger
and
Reading Phase-OFF
parameters.
Содержание Matrix 400
Страница 1: ...MATRIX 400 Reference Manual...
Страница 59: ...CBX ELECTRICAL CONNECTIONS 49 4 Figure 55 Matrix 400 Multidrop Connection to a Multiplexer...
Страница 62: ...MATRIX 400 REFERENCE MANUAL 52 4 Figure 57 ID NET Network Connections with isolated power blocks...
Страница 63: ...CBX ELECTRICAL CONNECTIONS 53 4 Figure 58 ID NET Network Connections with Common Power Branch Network...
Страница 64: ...MATRIX 400 REFERENCE MANUAL 54 4 Figure 59 ID NET Network Connections with Common Power Star Network...
Страница 81: ...19 PIN CONNECTOR ELECTRICAL CONNECTIONS 71 5 Figure 83 ID NET Network Connections with isolated power blocks...
Страница 82: ...MATRIX 400 REFERENCE MANUAL 72 5 Figure 84 ID NET Network Connections with Common Power Branch Network...
Страница 115: ...SOFTWARE CONFIGURATION 105 8 Figure 116 Options Communication Serial Port Figure 117 Options Communication Ethernet...
Страница 142: ...www automation datalogic com...