DKM-046 User Manual V-1.0
13
These parameters adjust the low temperature alarm limit for the
related sensor.
Adjustment range is between -
20°C and +80°C.
If the parameter is set to -
20°C then low temperature alarm is
not monitored for the related sensor.
As the default factory set, the alarm is passive.
These parameters adjust the high temperature alarm limit for
the related sensor.
Adjustment range is between -
20°C and +80°C.
If the parameter is set to
+80°C then high temperature alarm is
not monitored for the related sensor.
As the default factory set, the alarm is passive.
These parameters adjust the low relative humidity alarm limit for
the related sensor.
Adjustment range is between 1% and 99%.
If the parameter is set to 1% then low relative humudity alarm is
not monitored for the related sensor.
As the default factory set, the alarm is passive.
These parameters adjust the high relative humidity alarm limit
for the related sensor.
Adjustment range is between 1% and 99%.
If the parameter is set to 99% then high relative humudity alarm
is not monitored for the related sensor.
As the default factory set, the alarm is passive.
4.5 ADJUSTING RELATIVE HUMIDITY LOW AND HIGH LIMITS
4.4 ADJUSTING TEMPERATURE LOW AND HIGH LIMITS