DKM-046 User Manual V-1.0
17
0:
Alarm lock disabled
1:
Alarm lock enabled
When this parameter is set to 1, even if the alarm cause is
removed, alarms will persist until manually reset.
When this parameter is set to 0, when the alarm cause is
removed, alarms automatically disappear.
Factory set value is 0.
Adjustment range is 0 to 1.
This parameter determines the Modbus node address of the
unit. Every unit in the same Modbus loop must have a different
node address.
Factory set value is 1.
Adjustment range is 0 to 255.
This parameter determines the data rate (baud rate) used in the
Modbus communication. Every unit in the same Modbus loop
must use the same data rate.
0:
Baud rate = 2400
1:
Baud rate = 4800
2:
Baud rate = 9600
3:
Baud rate = 19200
4:
Baud rate = 38400
5:
Baud rate = 57600
6:
Baud rate = 115200
Factory set value is 2.
Adjustment range is 0 to 6.
4.9 ALARM LOCK
4.10 MODBUS PARAMETERS