DKM-046 User Manual V-1.0
19
These parameters determine respectively the high alarm limits
for temperature differences T1-T2, T2-T1, T2-T3, T3-T2, T3-T1,
T1-T3.
Adjustment range is between
0°C and 100°C.
Factory set value is 0 and the alarm is passive.
When this parameter is set to 0, the temperature difference
alarm is de-activated.
These parameters determine respectively the cooling start
upper limits for temperature sensors 1 , 2 and 3.
When the temperaure measured from the related sensor goes
over the programmed limit, then the cooling relay function will
become active. When the measured temperature goes below
the limit more than the programmed hysteresis value, then the
cooling relay function will become passive.
Adjustment range is between -21
°C and +80°C.
Factory set value is +40
°C.
4.14 ADJUSTING COOLING START TEMPERATURE UPPER LIMITS
4.13 ADJUSTING TEMPERATURE DIFFERENCE ALARM LIMITS