DKM-046 User Manual V-1.0
16
The factory set value for all relay functions is 0.
The adjustment range is from 0 to 14.
Each relay output is activated by the combination of 4 different
functions as explained above. Thus relay may be assigned to
complex functions.
Parameters at left adjust the function combination method for
each relay output.
0:
Functions are combined with logical OR operation. Thus if
any of the function is active, then the relay output is active.
1:
Functions are combined with logical AND operation. Thus the
relay output will be active only if all functions are active.
This parameter adjusts the delay for relay activation after all
conditions for relay operation are met.
The factory set value is 0.
Adjustment range is between 0 and 999 seconds.
This parameter adjusts the delay for alarm activation after an
alarm condition occurs. It also determines the delay for alarm
deactivation after the alarm condition is removed.
The factory set value is 0.
Adjustment range is between 0 and 999 seconds.