These parameters determine respectively the heating start
temperature limits for temperature sensors 1 , 2 and 3.
When the temperaure measured from the related sensor goes
below the programmed limit, then the heating relay function will
become active. When the measured temperature goes above
the limit more than the programmed hysteresis value, then the
heating relay function will become passive.
Adjustment range is between -
21°C and +80°C.
Factory set value is +20
°C.
These parameters determine respectively the hysteresis values
for stopping the heating or cooling for temperature sensors 1 , 2
and 3.
Adjustment range is between 0
°C and 100°C.
Factory set value is 5
°C.
These parameters determine respectively the de-humidification
start upper limits for humidity sensors 1 , 2 and 3.
When the relative humidity measured from the related sensor
goes over the programmed limit, then the de-humidification
relay function will become active. When the measured relative
humidity goes below the limit more than the programmed
hysteresis value, then the de-humidification relay function will
become passive.
Adjustment range is between 0% and +100%
Factory set value is 70%.
4.17 ADJUSTING DE-HUMIDIFICATION START HUMIDITY
4.16 ADJUSTING TEMPERATURE HYSTERESIS FOR COOLING
AND HEATING
4.15 ADJUSTING HEATING START TEMPERATURE LOW LIMITS