DKM-046 User Manual V-1.0
31
ADDR
ESS
NAME
DESCRIPTION
DIMENS
R/W
DATA TYPE
COEFFI
10609
Unit ID
Unit model type
16 BIT
R-O
unsigned word
1
20480
Sensor-1
temperature
16 BIT
R-O
signed word
0.01
20481
Sensor-1 relative
humidity
16 BIT
R-O
unsigned word
0.01
20482
Sensor-2
temperature
16 BIT
R-O
signed word
0.01
20483
Sensor-2 relative
humidity
16 BIT
R-O
unsigned word
0.01
20484
Sensor-3
temperature
16 BIT
R-O
signed word
0.01
20485
Sensor-3 relative
humidity
16 BIT
R-O
unsigned word
0.01
20486
Alarms
Alarm status bits
16 BIT
R-O
unsigned word
1
20487
Relay statuses
16 BIT
R-O
unsigned word
1
20488
T1-T2
temperature
difference
16 BIT
R-O
signed word
0.01
20489
T2-T3
temperature
difference
16 BIT
R-O
signed word
0.01
20490
T3-T1
temperature
difference
16 BIT
R-O
signed word
0.01
Alarm status record is 16 bit long. Each bit indicates the existence of one alarm.
BIT NO:
DESCRIPTION
0
-
1
Sensor-1 low temperature alarm
2
Sensor-1 high temperature alarm
3
Sensor-1 low humidity alarm
4
Sensor-1 high humidity alarm
5
Sensor-2 low temperature alarm
6
Sensor-2 high temperature alarm
7
Sensor-2 low humidity alarm
8
Sensor-2 high humidity alarm
9
Sensor-3 low temperature alarm
10
Sensor-3 high temperature alarm
11
Sensor-3 low humidity alarm
12
Sensor-3 high humidity alarm
13
T1-T2 temperature difference alarm
14
T2-T3 temperature difference alarm
15
T3-T1 temperature difference alarm
5.4. MEASUREMENTS AND CONTROLLER RECORDS