Program Group: Controller Configuration
Parameter Definition
Unit Factory
Set
Description
LCD Contrast
-
22
This parameter is used to set LCD contrast. Adjust for
the best viewing angle.
Language
-
0
0:
English language selected.
1:
Turkish language selected. This language may
depend on the country where the unit is intended to
be used.
2:
Chinese language selected
3:
The unit will ask for manual language selection at
power-on.
Line-to-Line Voltages
-
0
0:
Display Line to Neutral voltages as default
1:
Display Line to Line voltages as default
Genset Default Display
-
0
This parameter selects the screen which is displayed
during genset on load operation.
0:
screen 3 (or 4) electrical, large characters
1:
screen 5 engine parameters, large characters
2:
screen 6 (or 7) maximum information, small
characters
3:
screen 8 (or 9)
Details of each screen are explained in chapter 3.2
Fault Holdoff Timer
sec
12
This parameter defines the delay after the engine
runs and before the fault monitoring is enabled.
Alarm Relay Timer
sec
60
This is the period during which the
ALARM
relay is
active. If the period is set to 0, this will mean that the
period is unlimited.
Intermittent Alarm Relay
-
0
0:
continuous
1:
intermittent (turns on and off every second)
Charge Alternator Shutdown
-
0
0:
The charge input generates
CHARGE FAIL
warning, and does not stop the engine.
1:
The charge input generates
CHARGE FAIL
alarm,
and stops the engine.
Emergency Backup Mode
-
0
0:
In TEST mode, the load will not be transferred to
the genset even if the mains fail.
1:
In TEST mode, the load will be transferred to the
genset if the mains fail.
Exercise Day and Time
-
168
This parameter defines the start day and hour of the
exerciser.
Values higher or equal to 168 mean that the exerciser
is off.
The exercise may be selected to start at the
beginning of the any hour of the week. The parameter
value is the hour count of the start time.
Examples:
0 = exercise starts at Monday 00:00
8 = exercise starts at Monday 08:00
24 = exercise starts at Tuesday 00:00
167 = exercise starts at Sunday 23:00
168 = exerciser off
If a daily exercise is selected, then the day
information is don’t care and the exercise will be
performed every day regardless of the day selection.
If the monthly exerciser is selected, then the exercise
will be performed during the first 7 days of each
month at the programmed day and hour.