DKG-309 User Manual V-02
(11.05.2009)
- 34 -
Program Group: Adjust Date and Time
Parameter Definition
Unit Factory
Set
Description
Date
-
01-31 Current day of the month.
Month
-
01-12 Current month.
Year
-
00-99 Last two digits of the current year.
Hours
-
00-23 Current hour of the day.
Minutes
-
00-59 Current minute of the hour.
Seconds
-
00-59 Current second of the minute.
Program Group: Weekly Schedule
Parameter Definition
Unit Factory
Set
Description
Monday Turn_on
-
24:00
Please review chapter 9 for a detailed description of
weekly programming schedule operation.
Monday Turn_off
-
24:00
Tuesday Turn_on
-
24:00
Tuesday Turn_off
-
24:00
Wednesday Turn_on
-
24:00
Wednesday Turn_off
-
24:00
Thursday Turn_on
-
24:00
Thursday Turn_off
-
24:00
Friday Turn_on
-
24:00
Friday Turn_off
-
24:00
Saturday Turn_on
-
24:00
Saturday Turn_off
-
24:00
Sunday Turn_on
-
24:00
Sunday Turn_off
-
24:00
Program Group: Sender Characteristics
Parameter Definition
Unit Factory
Set
Description
Oil Pressure Sender Ohms -
1
ohm
10
Oil Pressure Sender point 1, ohm value
Oil Pressure Value -1
bar
0.0
Oil Pressure Sender point 1, bar value
Oil Pressure Sender Ohms -
2
ohm
52
Oil Pressure Sender point 2, ohm value
Oil Pressure Value -2
bar
2.0
Oil Pressure Sender point 2, bar value
Oil Pressure Sender Ohms -
3
ohm
90
Oil Pressure Sender point 3, ohm value
Oil Pressure Value -3
bar
4.0
Oil Pressure Sender point 3, bar value
Oil Pressure Sender Ohms -
4
ohm
140
Oil Pressure Sender point 4, ohm value
Oil Pressure Value -4
bar
7.0
Oil Pressure Sender point 4, bar value
Oil Pressure Sender Ohms -
5
ohm
156
Oil Pressure Sender point 5, ohm value
Oil Pressure Value -5
bar
8.0
Oil Pressure Sender point 5, bar value
Oil Pressure Sender Ohms -
6
ohm
184
Oil Pressure Sender point 6, ohm value
Oil Pressure Value -6
bar
10.0
Oil Pressure Sender point 6, bar value