background image

DKG-309 User Manual                                                                              V-02 

(11.05.2009)

 

 

 

 

 

 

- 29 -

 

 

 

Program Group: Controller Configuration (continued) 

Exercise Duration 

min 

10 

This parameter defines the exercise duration and 
programmed in 10 minute steps up to 24 hours. 

Exercise Off/On Load 

0:

 Exercise at 

TEST

 mode 

1:

 Exercise at 

LOAD TEST

 mode 

Exercise Period 

0:

 exercise every day (the exercise will be performed 

every day regardless of the day selection of Exercise 
Dat and Time parameter). 

1:

 exercise once per week 

2:

 exercise once per month (the exercise will be 

performed during the first 7 days of each month at the 
programmed day and hour). 

Remote Start Operation 

0:

 

NORMAL MODE:

 the engine runs when the mains 

fail. 

1: REMOTE START MODE:

 the engine runs when a 

signal from the 

SPARE-2

  input comes, the unit does 

not monitor mains voltages. 

Simulate Mains Operation 

0:

 The 

SPARE-2

input has normal function 

1:

 The 

SPARE-2 

input simulates mains. 

Delayed Simulate Mains 

0:

 The 

SPARE-2

 input has normal function 

1:

 The 

SPARE-2 

input has delayed simulate mains 

function. See chapter 6.8 for more info. 

Modem Enable 

0: 

No modem connection, the serial port is connected 

to PC

 

1: 

Modem connected. 

SMS Enable 

0:

 SMS not enabled 

1:

 SMS enabled 

GPRS Call Enable 

0: 

standard modem calls 

1:

 GPRS modem calls 

MODBUS Address 

0:

 RAINBOW communication protocol. 

1-144:

 MODBUS communication. This parameter is 

also the MODBUS controller address of the unit. 

Oil Pressure in psi 

0: 

oil pressure display in bars

 

1: 

oil pressure display in psi 

Temperature in °F 

0: 

temperature display in degrees C

 

1: 

temperature display in degrees F 

Flashing Relay Timer 

hours 

Delayed Simulate Mains Operation:

  max genset 

running time after Simulate Mains signal disappears. 

Dual Genset Systems:

 flashing relay toggle timer. 

Please contact DATAKOM for dual genset mutual 
stanby operation. 

Real Time Clock Adjust 

117 

This parameter trims precisely the real time clock 
circuit.  
Values from 0 to 63 speed up the clock with 
0.25sec/day steps.  
Values from 127 to 64 slow down the clock with 
0.25sec/day steps. 

Hysteresis Voltage 

This parameter provides the mains and genset voltage 
limits with a hysteresis feature in order to prevent 
faulty decisions. 
For example, when the mains are present, the mains 
voltage low limit will be used as the programmed low 
limit. When the mains fail, the low limit will be 
incremented by this value. It is advised to set this 
value to 8 volts. 

 
 

 

Содержание DKG-309

Страница 1: ...ging with date time stamp and complete measurement values Stores last 250 events Statistical counters Battery backed up real time clock Weekly operation schedule programs Programmable parameters All p...

Страница 2: ...d Mains Simulation Battery Charging 6 9 Dual Genset Mutual Standby Operation 6 10 Service Request Display 6 11 Engine Hours Meter 6 12 Date Time Display 6 13 Display of Software Version 6 14 Modem con...

Страница 3: ...e stored in a Non Volatile Memory and thus all information is retained even in the event of complete loss of power The measured parameters are Mains voltage phase L1 to neutral Mains voltage phase L2...

Страница 4: ...ach transformer to related inputs Never use common terminals or grounding The power rating of the transformer should be at least 5 VA It is recommended to s e g temperature oil pressure or fuel level...

Страница 5: ...nerator phases 6 MAINS NEUTRAL Input 0 300V AC Neutral terminal for the mains phases 7 MAINS L3 Mains phase inputs 0 300V AC Connect the mains phases to these inputs The mains voltages upper and lower...

Страница 6: ...elected via the program menu Each input may be driven by a normally closed or normally open contact switching either battery or battery The effect of the switch is also selectable from a list See PROG...

Страница 7: ...the programmed limits LOAD TEST Yellow It turns on when the related operation mode is selected One of these LEDs is always on and indicates which operation mode is selected If the operation of the gen...

Страница 8: ...ation between different screens s made with the MENU and MENU buttons Each depression of the MENU button switches the display to the next screen Each depression of the MENU button switches the display...

Страница 9: ...ttery Voltage Fuel Level 6 Complete Genset parameters phase to neutral Genset status Genset Volts L1 Genset Volts L2 Genset Volts L3 Genset Current L1 Genset Current L2 Genset Current L3 Genset Freque...

Страница 10: ...ion Date and time Operating software version 13 Statistical Counters 1 3 Engine Hours Run Total Genset Active Power KW h 14 Statistical Counters 2 3 Engine Hours to Service Time to Service 15 Statisti...

Страница 11: ...ion of the genset The existing alarms may be canceled by pressing one of the operating mode buttons LOAD TEST TEST OFF AUTO Most of the alarms have programmable trip levels See the programming chapter...

Страница 12: ...er This fault will be monitored with holdoff timer delay after the engine is running GENSET HIGH VOLTAGE Set if any of the generator phase voltages goes outside programmed limits for Overload Timer Th...

Страница 13: ...edule then the AUTO led will flash and the operation of the genset will be as in the OFF mode TEST It is used to test the generator when the mains are on or keep the generator running in the emergency...

Страница 14: ...ion The Fuel Level Sender Ohms is also programmable 6 3 Engine Heating Operation Especially on engines without a body heater or with a failing one it may be desired that the genset should not take the...

Страница 15: ...ters Also relays on an extension module may be assigned to this function The engine body temperature limit is adjusted using the parameter Engine Heating Temperature The same parameter is used for eng...

Страница 16: ...n both parameters Remote Start Operation and are set then REMOTE START operation mode is performed 8 Delayed Mains Simulation Battery Charging s Simulation feature is used in battery backed up telecom...

Страница 17: ...ching of the load between 2 gensets The use of 2 gensets instead of one is due either to safety purposes in case of a genset failure or to a continuous operation requesting service stops The running p...

Страница 18: ...month programmed values is zero this means that the parameter will not be used For example a maintenance indicates that the unit will request maintenance only based on engine hours gine hours is also...

Страница 19: ...cable network PSTN If the modem is connected to the unit the Modem Enable program parameter should be set to 1 otherwise faulty operation may occur If Modem Enable or SMS Enable or MODBUS Address par...

Страница 20: ...ges Any new upcoming alarm will result in a new GSM SMS message The new message will indicate all existing alarms even masked ones The necessary GSM modem cable will be supplied by DATAKOM This is the...

Страница 21: ...d hour Exercise off_load on_load Daily Weekly Monthly Please refer to the programming section for a more detailed description of the above When the start day and hour of exercise has come the unit wil...

Страница 22: ...d function consists on the connection of a dummy load if the total genset load is below a limit and to disconnection of the dummy load when the total power exceeds another limit The dummy load functio...

Страница 23: ...R W DATA SIZE COEFFICIENT DESCRIPTION 0000 R 16bit x1 Mains Phase L1 voltage 0001 R 16bit x1 Mains Phase L2 voltage 0002 R 16bit x1 Mains Phase L3 voltage 0003 R 16bit x1 Genset Phase L1 voltage 0004...

Страница 24: ...d in 10 minute steps Unused programs should be set to 24 00 An example setup may be as follows Monday Turn_on 07 00 Monday Turn_off 18 00 Tuesday Turn_on 07 00 Tuesday Turn_off 18 00 Wednesday Turn_on...

Страница 25: ...sured values are stored within the The events are recorded with a time stamp which comes from the internal real time The events are stored in a circular memory This means that a new coming event will...

Страница 26: ...unit if necessary with a soft damp cloth Do not use chemical agents STATISTICAL COUNTERS The unit provides a set of non resettable incremental counters for statistical purposes These counters are kept...

Страница 27: ...e made with and buttons Selected group is shown in reverse video blue on white In order to enter inside a group please press MENU button In order to exit from the group to the main list please press M...

Страница 28: ...RM relay is active If the period is set to 0 this will mean that the period is unlimited Intermittent Alarm Relay 0 0 continuous 1 intermittent turns on and off every second Charge Alternator Shutdown...

Страница 29: ...port is connected to PC 1 Modem connected SMS Enable 0 0 SMS not enabled 1 SMS enabled GPRS Call Enable 0 0 standard modem calls 1 GPRS modem calls MODBUS Address 0 0 RAINBOW communication protocol 1...

Страница 30: ...vercurrent check is disabled Excess Power Limit KW 0 If the active power goes above this limit during the period defined in Overload Timeout then an Excess Power Load Dump alarm will be generated If t...

Страница 31: ...entered within the limits and the generator contactor is deactivated Genset Contactor Timer sec 1 This is the period after the mains contactor has been deactivated and before the generator contactor h...

Страница 32: ...EMPERATURE SENDER warning High Temperature Shutdown C 98 f the coolant temperature measured from the analog input goes over this limit this will generate a HIGH TEMPERATURE SENDER alarm and the engine...

Страница 33: ...0 engine is heated during Engine Heating Timer 1 engine is heated until the coolant temperature reaches the Engine Heating Temperature and at least during the Engine Heating Timer Service Engine Hours...

Страница 34: ...Turn_off 24 00 Sunday Turn_on 24 00 Sunday Turn_off 24 00 Program Group Sender Characteristics Parameter Definition Unit Factory Set Description Oil Pressure Sender Ohms 1 ohm 10 Oil Pressure Sender...

Страница 35: ...Temperature Sender point 2 C value Temperature Sender Ohms 3 ohm 134 Temperature Sender point 3 ohm value Temperature Value 3 C 60 Temperature Sender point 3 C value Temperature Sender Ohms 4 ohm 322...

Страница 36: ...lly open 1 Normally closed Switching 0 0 Battery negative 1 Battery positive Response delay 0 0 No delay 1 Delayed 4sec Program Group Input Configuration High Temperature Switch Parameter Definition U...

Страница 37: ...e engine stops immediately 1 Load Dump the engine stops after cooldown 2 Warning the horn relay operates 3 No operation Sampling 2 0 Always 1 After holdoff timer 2 When mains present Latching 1 0 Non...

Страница 38: ...e stops immediately 1 Load Dump the engine stops after cooldown 2 Warning the horn relay operates 3 No operation Sampling 0 0 Always 1 After holdoff timer 2 When mains present Latching 0 0 Non latchin...

Страница 39: ...ected from list Relay 06 Definition 5 RELAY 6 function expansion module 1 selected from list Relay 07 Definition 0 RELAY 7 function expansion module 1 selected from list Relay 08 Definition 2 RELAY 8...

Страница 40: ...p sender alarm 42 Low speed alarm 43 High speed alarm 44 Low voltage alarm 45 High voltagealarm 46 Fail to start alarm 47 Low fuel sender alarm 48 49 50 51 High battery voltage alarm 52 Charge fail al...

Страница 41: ...r in order to enable dialing through a pabx Program Group Modem 2 SMS 1 Telephone Number Parameter Definition Factory Set Description Modem 2 SMS 1 telephone number This telephone number buffer accept...

Страница 42: ...Genset Voltage L1 Calibration 760 Adjusts the measurement of genset voltage of phase L1 Genset Voltage L2 Calibration 760 Adjusts the measurement of genset voltage of phase L2 Genset Voltage L3 Calib...

Страница 43: ...frequency displayed on the unit are not correct Check engine body grounding it is necessary The error margin of the unit is 3 volts If there are faulty measurements only when the engine is running the...

Страница 44: ...an auxiliary relay The coil of the relay will be between BATTERY and charging alternator D terminal The normally closed contact of the relay will be connected serially to the unit s START output So th...

Страница 45: ...e EU directives 2006 95 EC low voltage 2004 108 EC electro magnetic compatibility Norms of reference EN 61010 safety requirements EN 61326 EMC requirements The CE mark indicates that this product comp...

Страница 46: ...10 to 30 VDC Current inputs from current transformers 5A Max load 0 7VA per phase Digital inputs input voltage 0 30 VDC Internally connected to battery positive via 4700 ohm resistor Analog inputs Re...

Страница 47: ...DKG 309 User Manual V 02 11 05 2009 47 15 CONNECTION DIAGRAM...

Страница 48: ...ERROR stackunderflow OFFENDING COMMAND STACK...

Отзывы: