DKG-309 User Manual V-02
(11.05.2009)
- 35 -
Program Group: Sender Characteristics (continued)
Parameter Definition
Unit Factory
Set
Description
Temperature Sender Ohms -
1
ohm
38
Temperature Sender point 1, ohm value
Temperature Value -1
°C
100
Temperature Sender point 1, °C value
Temperature Sender Ohms -
2
ohm
51
Temperature Sender point 2, ohm value
Temperature Value -2
°C
90
Temperature Sender point 2, °C value
Temperature Sender Ohms -
3
ohm
134
Temperature Sender point 3, ohm value
Temperature Value -3
°C
60
Temperature Sender point 3, °C value
Temperature Sender Ohms -
4
ohm
322
Temperature Sender point 4, ohm value
Temperature Value -4
°C
39
Temperature Sender point 4, °C value
Temperature Sender Ohms -
5
ohm
650
Temperature Sender point 5, ohm value
Temperature Value -5
°C
20
Temperature Sender point 5, °C value
Temperature Sender Ohms -
6
ohm
1630
Temperature Sender point 6, ohm value
Temperature Value -6
°C
02
Temperature Sender point 6, °C value