DKG-309 User Manual
(11.05.2009)
When the signal is passive, the unit will revert to normal operation and monitor the mains
voltage status.
The REMOTE START operation overrides
operation. When both parameters
“Delayed Simulate
is performed.
6.9 Dual Genset Mutual Standby
Dual genset intermittent operation
The use of 2 gensets instead of one is due either to safety p
continuous operation requesting service s
The running period for each genset is adjustable using
parameter. If the time is adjusted as 0 hours, it will be actually set to 2 minutes for faster testing
purposes.
A flashing relay output function is provided, based on the parameter
Each time the period programmed using
position.
The flashing relay function may be assigned to spare relays usi
parameters. Also relays on an extension module may be assigned to this function.
The dual genset intermittent operation uses also the
chapter
6.7
for a detailed explanation of this feature
Please contact DATAKOM for a complete application manual.
When the signal is passive, the unit will revert to normal operation and monitor the mains
The REMOTE START operation overrides DELAYED SIMULATE MAINS
When both parameters “Remote Start Operation” and
Simulate Mains” are set then REMOTE START
Mutual Standby Operation
Dual genset intermittent operation consists of regular switching of the load between 2 gensets.
The use of 2 gensets instead of one is due either to safety purposes in case of a genset failure or to a
continuous operation requesting service stops.
The running period for each genset is adjustable using
Flashing Relay Timer
. If the time is adjusted as 0 hours, it will be actually set to 2 minutes for faster testing
shing relay output function is provided, based on the parameter
Flashing Relay Timer
Each time the period programmed using
Flashing Relay Timer
elapses, the relay output will change
The flashing relay function may be assigned to spare relays using
Relay Definition
parameters. Also relays on an extension module may be assigned to this function.
The dual genset intermittent operation uses also the
Mains Simulation
feature. Please review
for a detailed explanation of this feature.
Please contact DATAKOM for a complete application manual.
V-02
- 17 -
When the signal is passive, the unit will revert to normal operation and monitor the mains
SIMULATE MAINS
“Remote Start Operation” and
REMOTE START operation mode
consists of regular switching of the load between 2 gensets.
rposes in case of a genset failure or to a
Flashing Relay Timer
program
. If the time is adjusted as 0 hours, it will be actually set to 2 minutes for faster testing
Flashing Relay Timer
.
ses, the relay output will change
Relay Definition
program
parameters. Also relays on an extension module may be assigned to this function.
feature. Please review
Please contact DATAKOM for a complete application manual.