D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 72 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
092-Load Subtract-Add
Delay
min
0
120
0
This is the minimum delay required for a
load_add pulse after a load_substract
pulse.
Review chapter “Load Shedding”
for more details.
093-Mains Waiting Timer
sec
0
50000
30
This is the time between the mains
voltages and frequency entered within
the limits and the generator contactor is
deactivated.
094-Mains Connection
Topology
-
0
7
5
This is the connection topology of mains
voltages and CTs. Detailed
explanations are given in the chapter:
“TOPOLOGIES”.
0:
2 phase, 3 wire L1-L2
1:
2 phase, 3 wire L1-L3
2:
3 phase, 3 wire
3:
3 phase, 3 wire, 2CTs L1-L2
4:
3 phase, 3 wire, 2CTs L1-L3
5:
3 phase, 4 wire star
6:
3 phase, 4 wire delta
7:
single phase, 2 wire
095-Genset Connection
Topology
-
0
7
5
This is the connection topology of
genset voltages and CTs. Detailed
explanations are given in the chapter:
TOPOLOGIES.
0:
2 phase, 3 wire L1-L2
1:
2 phase, 3 wire L1-L3
2:
3 phase, 3 wire
3:
3 phase, 3 wire, 2CTs L1-L2
4:
3 phase, 3 wire, 2CTs L1-L3
5:
3 phase, 4 wire star
6:
3 phase, 4 wire delta
7:
single phase, 2 wire
096-Mains Contactor
Timer
sec
0
600
0.5
This is the period after the generator
contactor has been deactivated and
before the mains contactor has been
activated.
097-Mains MCB Close
Pulse
sec
0
10
0.5
After the mains MCB_undervoltage coil
is energized and mains
MCB_undervoltage coil timer is
elapsed, the mains MCB_close relay
will be activated during this period.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
098-Mains MCB Open
Pulse
sec
0
10
0.5
The mains MCB_open relay will be
activated during this period.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
099-Mains MCB Under
Voltage Coil Timer
sec
0
10
0.5
The mains MCB_undervoltage coil is
energized during this period before the
mains MCB_close relay is activated.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
100-MCB Alarm Level
-
0
1
0
0:
shutdown alarm
1:
loaddump alarm
Содержание D-100 MK2
Страница 29: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 29 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 30: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 30 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 4 4 3 PHASE 4 WIRE DELTA ...
Страница 32: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 32 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 35: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 35 6 CONNECTION DIAGRAMS 6 1 AMF FUNCTIONALITY CTs AT LOAD SIDE ...
Страница 36: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 36 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Страница 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Страница 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...