D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 23 -
Structure:
RS-485, isolated.
Connection:
3 wires (A-B-GND). Half duplex.
Baud rate:
2400-38400 bauds, selectable
Data type:
8 bit data, no parity, 1 bit stop
Termination:
External 120 ohms required
Isolation:
250VAC, 1 minute
Common mode voltage:
-0.5 VDC to +7VDC, internally clamped by transient suppressors.
Max distance:
1200m @ 9600 bauds (with 120 ohms balanced cable)
The RS-485 port features MODBUS-RTU protocol. Multiple modules (up to 128) can be paralleled on the
same RS-485 bus for data transfer to automation or building management systems.
The RS-485 port provides also a good solution for distant PC connection where RainbowPlus program
will enable programming, control and monitoring.
For more details about programming, control and
monitoring through RS-485 port please refer to
RainbowPlus user manual.
The Modbus register list is available at Datakom
technical support.
3.12. RS-485 PORT (PLUG-IN MODULE)
3.11. -
RS-485 Slot
Содержание D-100 MK2
Страница 29: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 29 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 30: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 30 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 4 4 3 PHASE 4 WIRE DELTA ...
Страница 32: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 32 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 35: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 35 6 CONNECTION DIAGRAMS 6 1 AMF FUNCTIONALITY CTs AT LOAD SIDE ...
Страница 36: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 36 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Страница 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Страница 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...