D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 75 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
131-Start Request Timer
sec
0
1800
30
This is the maximum delay after the
ATS controller issues a Remote Start
command and genset voltage are
established.
132-Preheat Timer
sec
0
30
0
This is the time after the fuel solenoid is
energized and before the genset is
started. During this period the
PREHEAT
relay output is energized (if
assigned by
Relay Definitions
)
133-Crank Timer
sec
1
15
6
This is the maximum start period.
Starting will be automatically cancelled
if the genset fires before the timer.
134-Wait Between Starts
sec
1
240
10
This is the waiting period between two
start attempts.
135-Engine Heating
Timer
sec
0
240
4
This is the period used for engine
heating before load transfer.
136-Engine Heating
Method
-
0
1
0
The genset will not take the load before
engine heating is completed.
0:
engine is heated during
Engine
Heating Timer
.
1:
engine is heated until the coolant
temperature reaches the
Engine
Heating Temperature
and at least
during the
Engine Heating Timer
.
137-Cooldown Timer
sec
0
600
120
This is the period that the generator runs
for cooling purpose after the load is
transferred to mains.
138-Stop Solenoid Timer
sec
0
90
10
This is the maximum time duration for
the engine to stop. During this period
the STOP relay output is energized (if
assigned by
Relay Definitions
). If the
genset has not stopped after this
period, a
FAIL TO STOP
warning
occurs.
139-Number of Starts
-
1
6
3
Number of Start attempts
140-Choke Timer
sec
0
240
5
This is the control delay of CHOKE
output.
The choke output is activated together
with the crank output. It is released after
this delay or when engine runs
(whichever occurs first).
141-Idle Speed (Run)
Timer
sec
0
240
0
When the engine runs, the Idle output
relay function will be active during this
timer. While the IDLE output is active,
low voltage, low frequency and low rpm
checks are disabled.
142-Idle Speed (Stop)
Timer
sec
0
240
0
Before the engine stops, the Idle output
relay function will be active during this
timer. While the IDLE output is active,
low voltage, low frequency and low rpm
checks are disabled.
143-Idle Holdoff Timer
sec
0
30
10
While the IDLE period is over, low
voltage, low frequency and low speed
checks are enabled after the expiration
of this timer.
Содержание D-100 MK2
Страница 29: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 29 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 30: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 30 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 4 4 3 PHASE 4 WIRE DELTA ...
Страница 32: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 32 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 35: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 35 6 CONNECTION DIAGRAMS 6 1 AMF FUNCTIONALITY CTs AT LOAD SIDE ...
Страница 36: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 36 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Страница 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Страница 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...