D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 59 -
ALARM #
LOADDUMP#
WARNING#
DESCRIPTION
55
311
567
HIGH OIL PRESSURE:
Set if the oil pressure value measured from the sender is
above the programmed limit. Warning and shutdown limits
are independently programmable. This fault will be
monitored
Holdoff Timer
delay after the engine is running.
56
312
568
LOW COOLANT TEMPERATURE:
Set if the coolant temperature value measured from the
sender is below the programmed limit. Warning and
shutdown limits are independently programmable.
57
313
569
HIGH COOLANT TEMPERATURE:
Set if the coolant temperature value measured from the
sender is above the programmed limit. Warning and
shutdown limits are independently programmable.
58
314
570
LOW FUEL LEVEL:
Set if the fuel level value measured from the sender is
below the programmed limit. Warning and shutdown limits
are independently programmable.
59
315
571
HIGH FUEL LEVEL:
Set if the fuel level value measured from the sender is
above the programmed limit. Warning and shutdown limits
are independently programmable.
60
316
572
OIL SENDER OPEN:
Set if the resistor value read from the sender input is
above 5000 ohms or if the terminal is left open.
61
317
573
TEMPERATURE SENDER OPEN:
Set if the resistor value read from the sender input is
above 5000 ohms or if the terminal is left open.
62
318
574
FUEL LEVEL SENDER OPEN:
Set if the resistor value read from the sender input is
above 5000 ohms or if the terminal is left open.
63
319
575
LOW BATTERY VOLTAGE:
Set if the genset battery voltage is below programmed
limits. Shutdown and warning limits are independently
programmable. The detection delay is also programmable.
64
320
576
HIGH BATTERY VOLTAGE:
Set if the genset battery voltage is above programmed
limits. Shutdown and warning limits are independently
programmable. The detection delay is also programmable.
65
321
577
FAIL TO START:
Set if the engine is not running after programmed number
of start attempts.
66
322
578
FAIL TO STOP:
Set if the engine has not stopped before the expiration of
the
Stop Timer
.
67
323
579
LOW CHARGE VOLTAGE:
Set if the charge alternator voltage is below the
programmed limit. This fault will be monitored with
Fault
Holdoff Timer
delay after the engine is running.
Содержание D-100 MK2
Страница 29: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 29 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 30: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 30 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 4 4 3 PHASE 4 WIRE DELTA ...
Страница 32: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 32 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 35: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 35 6 CONNECTION DIAGRAMS 6 1 AMF FUNCTIONALITY CTs AT LOAD SIDE ...
Страница 36: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 36 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Страница 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Страница 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...