D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 70 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
067-Genset High
Frequency Warning Limit
%
F-100 F+100 F+15%
If the genset frequency goes over this
limit when feeding the load, this will
generate a
GENSET HIGH
FREQUENCY
warning.
068-Genset High
Frequency Shutdown
Limit
%
F-100 F+100 F+20%
If the genset frequency goes over this
limit when feeding the load, this will
generate a
GENSET HIGH
FREQUENCY
shutdown alarm and the
engine will stop.
069-Genset Frequency
Fail Timer
sec
0
10
1
If the genset frequency goes outside of
the limits during this timer, a genset
frequency fault will occur.
070-Low Battery Voltage
Warning Limit
V-DC
5.0
35.0
12.0
If the battery voltage falls below this
limit, this will generate a
LOW
BATTERY
warning.
071-Low Battery Voltage
Shutdown Limit
V-DC
5.0
35.0
9.0
If the battery voltage falls below this
limit, this will generate a
LOW
BATTERY
shutdown
alarm and the
engine will stop.
072-High Battery Voltage
Warning Limit
V-DC
5.0
35.0
29.0
f the battery voltage goes over this limit,
this will generate a
HIGH BATTERY
warning.
073-High Battery Voltage
Shutdown Limit
V-DC
5.0
35.0
30.0
If the battery voltage goes over this
limit, this will generate a
HIGH
BATTERY
shutdown
alarm and the
engine will stop.
074-Battery Voltage Fail
Timer
sec
0
10
3
If the battery voltage goes outside of the
limits during this timer, a battery voltage
fault will occur.
075-Genset Voltage
Unbalance Limit
%
0
100
0.0
If any genset phase voltage differs from
the average more than this limit, it will
generate a Voltage Unbalance fault
condition. The action taken upon fault
condition is programmable.
If this parameter is set to 0.0 then
voltage unbalance is not monitored
076-Genset Voltage
Unbalance Action
-
0
3
0
0:
no action
1:
shutdown alarm
2:
loaddump alarm
3:
warning
077-Genset Current
Unbalance Limit
%
0
100
0.0
If any genset phase current differs from
the average more than this limit, it will
generate a Current Unbalance fault
condition. The action taken upon fault
condition is programmable.
If this parameter is set to 0.0 then
voltage unbalance is not monitored
078-Genset Current
Unbalance Action
-
0
3
0
0:
no action
1:
shutdown alarm
2:
loaddump alarm
3:
warning
079-Genset Reverse
Power Warning Limit
kW
0
50000
0
If the genset power is negative and
goes above this limit then a
REVERSE
POWER
warning will be generated. If
this parameter is set to 0 then reverse
power fault is not monitored.
Содержание D-100 MK2
Страница 29: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 29 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 30: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 30 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 4 4 3 PHASE 4 WIRE DELTA ...
Страница 32: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 32 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 35: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 35 6 CONNECTION DIAGRAMS 6 1 AMF FUNCTIONALITY CTs AT LOAD SIDE ...
Страница 36: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 36 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Страница 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Страница 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...