D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 74 -
Parameter Definition
Unit
Min
Max
Factor
y Set
Description
116-Excess power
Warning Limit
kW
0
50000
0
If the genset active power goes above
this limit then the controller will give an
Excess Power Warning.
117-Nominal RPM
rpm
0
50000
1500
The nominal value of engine rpm. Low-
high rpm limits are defined by reference
to this value.
118-Nominal RPM-2
rpm
0
50000
1800
When secondary frequency is selected,
this is the nominal value of engine rpm.
Low-high rpm limits are defined by
reference to this value.
119-Nominal RPM-3
rpm
0
50000
1800
When tertiary frequency is selected, this
is the nominal value of engine rpm. Low-
high rpm limits are defined by reference
to this value.
120-Low RPM Warning
Limit
%
R-100 R+100
R-10%
If the engine rpm goes under this limit
when feeding the load, this will generate a
GENSET LOW RPM
warning.
121-Low RPM Shutdown
Limit
%
R-100 R+100
R-15%
If the engine rpm goes under this limit
when feeding the load, this will generate a
GENSET LOW RPM
shutdown alarm
and the engine will stop.
122-High RPM Warning
Limit
%
R-100 R+100 R+10%
If the engine rpm goes over this limit
when feeding the load, this will generate a
GENSET HIGH RPM
warning.
123-High RPM
Shutdown Limit
%
R-100 R+100 R+15%
If the engine rpm goes over this limit
when feeding the load, this will generate a
GENSET HIGH RPM
shutdown alarm
and the engine will stop.
124-RPM Fail Timer
sec
0
10
3
If the engine rpm goes outside of the
limits during this timer, an engine speed
fault will occur.
125-Overspeed
Overshoot Limit
%
HRSL
-100
HRSL
+100
HRSL
+10%
If the engine rpm
goes over the “High
RPM Shutdown Limit” by this quantity,
this will generate immediately a
GENSET
HIGH RPM
shutdown alarm and the
engine will stop.
126-Low Charge Voltage
Warning Limit
V-DC
0
40
6.0
If the charge alternator voltage goes
under this limit, a charge alternator
voltage warning will occur.
127-Low Charge Voltage
Shutdown Limit
V-DC
0
40
4.0
If the charge alternator voltage goes
under this limit, a charge alternator
voltage shutdown will occur and the
engine will stop.
128-Charge Voltage Fail
Timer
sec
0
120
1
If the charge alternator voltage goes
under limits during this timer, a charge
alternator voltage fault will occur.
129-Engine Heating
Temperature
°C
0
80
0
If it is requested that the engine runs
without load until reaching a certain
temperature, this parameter defines the
temperature.
130-Engine Start Delay
min
0
720
1
This is the time between the mains fails
and the fuel solenoid turns on before
starting the genset. It prevents
unwanted genset operation in battery
backed-up loads.
Содержание D-100 MK2
Страница 29: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 29 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 30: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 30 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 4 4 3 PHASE 4 WIRE DELTA ...
Страница 32: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 32 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 35: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 35 6 CONNECTION DIAGRAMS 6 1 AMF FUNCTIONALITY CTs AT LOAD SIDE ...
Страница 36: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 36 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Страница 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Страница 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...