D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 67 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
029-Reverse CT
Direction
-
0
1
0
This parameter is useful to invert all CT
polarities at the same time.
0: normal CT polarity assumed.
1: reverse CT polarity assumed.
030-Unit Functionality
-
0
3
AMF
0: AMF functionality. The unit controls
both engine and load transfer. The
genset starts based on mains status.
1: ATS functionality. The unit controls
the load transfer and issues genset start
signal based on mains status.
2: REMOTE START functionality. The
unit controls engine and alternator. The
genset starts with external signal.
3: RESERVED. Not used.
031-Change Level-1
Password
-
0000
9999
1234
Level-1 password may be modified with
this parameter
032-Change Level-2
Password
-
0000
9999
9876
Level-2 password may be modified with
this parameter
033-LCD Backlight
Dimming Delay
min
0
1440
60
If no button is pressed during this
period, then the unit will reduce the LCD
screen backlight intensity in for
economy.
034-Fuel Filling Timer
sec
0
36000
0
After activation of the fuel pump
function, if the Fuel Pump High Limit
level is not reached, then the fuel pump
will stop for safety.
If this parameter is set to zero, then the
timer is unlimited.
035-Open with Last
Mode
-
0
1
0
0: The unit powers up in STOP mode
1: The unit powers up in the same
operating mode before power down.
036-Pre-Transfer Delay
sec
0
60
0
If this parameter is not zero, the unit will
activate the Wait Before Transfer output
function during this timer, before
initiating a load transfer.
This function is designed for elevator
systems, in order to bring the cabin to a
floor and open doors before transfer.
037-Enable Auto not
Ready Warning
-
0
1
0
0: Auto not Ready Warning disabled
1: Auto not Ready Warning enabled
038-SMS on Engine
Run/Stop
-
0
1
0
This parameter controls SMS sending
when the engine runs or stops. No
warnings generated.
0: no SMS on engine run/stop
1: SMS sent on engine run/stop
039-Dual Genset Equal
Aging Enabled
-
0
1
0
0: Equal aging not enabled
1: Equal aging enabled
040-CT Secondary
Rating
-
0
1
0
0: xxx/5A
1: xxx/1A
041-Maintenance Done
Warning Enable
-
0
1
0
If enabled, the unit will generate a non-
visual warning when maintenance
counters are reset. In consequence,
SMS will be sent, the warning will be
visible on the central monitoring system.
0: maintenance warning disabled
1: maintenance warning enabled
Содержание D-100 MK2
Страница 29: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 29 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 30: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 30 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 4 4 3 PHASE 4 WIRE DELTA ...
Страница 32: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 32 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 35: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 35 6 CONNECTION DIAGRAMS 6 1 AMF FUNCTIONALITY CTs AT LOAD SIDE ...
Страница 36: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 36 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Страница 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Страница 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...