background image

dap

  

 4

Installation, Operation  

& Maintenance Manual

TM

Data Aire, Inc.

230 W. BlueRidge Avenue

Orange, CA  92865

www.dataaire.com

Содержание dap4 touch

Страница 1: ...dap 4 Installation Operation Maintenance Manual TM Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...

Страница 2: ...Data Aire Inc reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice...

Страница 3: ...Changing the Service Level Password 12 Menus Menu A ON OFF 13 Menu B Setpoints 14 Menu C Clock Scheduler 16 Menu D Input Output 20 Menu E Historical Data 23 Menu F Information 25 Menu G Network Confi...

Страница 4: ......

Страница 5: ...mable solid state control module LED Illuminated Keys Six highly reliable keys allow movement through the menus Backlit Liquid Crystal Display LCD Information is displayed and presented in a format t...

Страница 6: ...c Compressor Rotation Periodically rotates the lead lag compressor sequence to balance run times Automatic Reheat Element Rotation Rotates the staging sequence to balance the heating elements run time...

Страница 7: ...may require additional components and or sensors WARNINGS AND ALARMS DISPLAYED HIGH TEMPERATURE WARNING LOW TEMPERATURE WARNING HIGH HUMIDITY WARNING LOW HUMIDITY WARNING POWER FAILURE RESTART NO AIR...

Страница 8: ...RESTART RESTART MODE SYSTEM START DELAY MANUAL DIAGNOSTICS MESSAGE FOR OPTIONAL ALARM 1 2 3 and 4 PERSON TO CONTACT ON ALARM DELAY FOR OPTIONAL ALARM 1 2 3 and 4 WATER VALVE MODE COMPRESSOR ASSIST TO...

Страница 9: ...The display panel has a backlit LCD liq uid crystal display There are six keys on the face of the display panel to retrieve or enter settings Control Module Display Module Button Functions Allows vie...

Страница 10: ...urned ON at any time Hold the Esc key for approximately 5 seconds The dis play will continue to scroll and display messages At the same time the unit status is changed to Unit On Once powered there wi...

Страница 11: ...Level Password setting from the factory is 0000 The cursor will be flashing by the Security Access message at the top of the screen Press the ENTER key to move the cursor The cursor will flash at the...

Страница 12: ...e changed by doing the following Enter the Main Menu by pressing the Menu key You will be prompted to Insert the Service Level password Enter the current password as previously explained Press the Men...

Страница 13: ...s the ENTER key to save the setting If selecting SWITCH OFF the STATUS will change to OFFbyKey The unit will be OFF If selecting SWITCH ON the STATUS will change to UnitOn The unit will be ON When swi...

Страница 14: ...nge for CW 65 105 F DEADBAND 2 0 F Temperature Deadband range 2 5 F STAGE TO STAGE 0 3 F Stage to Stage range 0 3 3 0 F ENGY SVR SETPT 50 0 F Setpoint range 40 0 60 0 F DEADBAND 1 0 F Deadband range 1...

Страница 15: ...nce the desired setpoint value has been changed press the ENTER key to move to the next setting or until the cursor is at the top of the screen Exit the Setpoint Menu by pressing the Esc key The displ...

Страница 16: ...the UP and DOWN keys will change the value The day will automatically change when the date has been altered Press the ENTER key until the cursor is in the title block upper left hand corner Press the...

Страница 17: ...ected Press the ENTER key The cursor will flash on the Copy to Day Pressing the UP or DOWN key all the days of the week can be viewed The Copy to function allows the user to copy setting from other da...

Страница 18: ...e Once the correct minutes are selected press the Enter key The cursor will be positioned on the settings input Press the DOWN key to view the available selections Set Back Normal SP setpoint Turn Off...

Страница 19: ...Normal SP Turn Off Set Back Once the settings are complete with the cursor in the title block press the DOWN key to advance to the next screen or press Esc to return to the Main Menu or press the Esc...

Страница 20: ...menus Scroll through the menus using either the UP or DOWN keys Move Menu D to the highlighted area and press the ENTER key The following will be displayed values are for reference only Press the DOW...

Страница 21: ...reference only Press the DOWN key to view the next screen The following will be displayed values are for reference only Press the DOWN key to view the next screen The following will be displayed value...

Страница 22: ...ues are for reference only All screens have been viewed BY pressing the UP or DOWN keys the screens can be viewed Press the MENU key to return to the main menu Choose another menu by pressing the UP o...

Страница 23: ...NTER key moving the cursor into the screen area Press the UP key and the display will show the previous alarm with time and date Continue to press the UP key to view all alarms Once the last listed al...

Страница 24: ...ntil the cursor is flashing on the title line Press the DOWN key to move to next screen The screen will display the following With the cursor flashing on the title line press the UP or Down key to rev...

Страница 25: ...two screens The first screen will display the following Press the UP or DOWN key to view second screen The second screen will display the following Press the MENU key to return to the main menu or pr...

Страница 26: ...on has been made press the ENTER key and the cursor will move to the title block To move to the next screen press the DOWN key The following will be displayed values are for reference only The address...

Страница 27: ...increase or DOWN to decrease keys the Offset can be changed Once the change has been made press the ENTER key and the cursor will move to the title block of the screen The Offset change is now entere...

Страница 28: ...ove the cursor The cursor will flash at the Offset By pressing the UP to increase or DOWN to decrease keys the Offset can be changed Once the change has been made press the ENTER key and the cursor wi...

Страница 29: ...u press the Esc key or to view the following screen press the DOWN key The following will be displayed values are for reference only Move the cursor to the title block by pressing the ENTER key To ret...

Страница 30: ...llowing will be displayed values are for reference only Move the cursor to the title block by pressing the ENTER key To return to the Main Menu press the Esc key or to view the following screen press...

Страница 31: ...0 to 99 seconds in 1 second intervals Start up Delay The range is 5 to 600 seconds in 1 second intervals Temp Units Fahrenheit or Centigrade Out Status There are five choices Sys On Dehum On Hum On Co...

Страница 32: ...can be entered Modulate Min 40 100 Modulate Max 70 100 If choosing AIR PRESSURE the following will be displayed and values can be entered Modulate Min 40 100 Modulate Max 70 100 With DX if choosing PR...

Страница 33: ...l semi hermetic compressors w unloading Four Tandem dual tandem scroll compressors None entry for chilled water units Lead Lag Enabled or Disabled if Disabled is selected Lead and Rotate Lead are not...

Страница 34: ...e of refrigerant suction pressure Move the cursor to the title block by pressing the ENTER key stepping through all the inputs To return to the main Menu press the Esc key or to view the following scr...

Страница 35: ...econd factory setting is First With three stage reheat pick either First Second or Third factory setting is First Once a selection or selections have been made move the cursor to the title block by pr...

Страница 36: ...there will be no message Note E Saver Assist will only appear if either Engy Svg Cool or Aux Chill Wtr are selected Wtr Vlv Voltage 0 10 factory setting 4 7 6 9 7 10 2 10 Wtr Vlv Action Direct factor...

Страница 37: ...r selections have been made move the cursor to the title block by pressing the ENTER key or press the Esc key to return normal operating mode Press the DOWN key to view the next screen The following w...

Страница 38: ...tions Yes or No Note Selecting YES will reset all values back to the factory settings default If YES is selected the following message will be displayed wait resetting resetting will take a few second...

Страница 39: ...ce only Available Selections Audio Mode None Full On Long Beep Short Beep Pwr Up Auto No Alarm Auto With Alarm Man Clr Alarm Maint Due Msg None The range is 0 to 1000 hours Once a selection or selecti...

Страница 40: ...e the cursor to the title block by pressing the ENTER key Press the DOWN key to view the next screen The following will be displayed values are for reference only Available Selections No Water Flow Ac...

Страница 41: ...F factory setting is 60 F Note If No is selected for the Hi or Lo Temp Alarm the Set Point will not be displayed Once a selection or selections have been made move the cursor to the title block by pre...

Страница 42: ...to 90 RH factory setting is 60 RH Lo Humidity Alarm Yes or No factory setting is Yes Set Point The range is 10 to 65 RH factory setting is 40 RH Note If No is selected for the Hi or Lo Humidity Alarm...

Страница 43: ...PUMP ON UPS ON CHK MAIN POWER UNIT IN STBY REHEAT HUM INHIBIT HUMIDIFIER INHIBITED REHEAT INHIBITED Once a selection or selections have been made move the cursor to the title block by pressing the EN...

Страница 44: ...ENTER key Press the DOWN key to view the next screen The following will be displayed values are for reference only Alarm Output Function 1 See sample screen shot at end of section Alarm 1 Alarm 2 Alar...

Страница 45: ...or No Low Humid Yes or No Yes or No Yes or No Yes or No Humidifier Yes or No Yes or No Yes or No Yes or No DA Low T Yes or No Yes or No Yes or No Yes or No RA Low T Yes or No Yes or No Yes or No Yes o...

Страница 46: ...es or No Yes or No Yes or No Yes or No Alm SW 4 Yes or No Yes or No Yes or No Yes or No Once a selection or selections have been made move the cursor to the title block by pressing the ENTER key Press...

Страница 47: ...the ENTER key Move the cursor to change the setting The following can be changed by pressing the DOWN key Channel Open or Closed Delay the range is 0 999 seconds Status Open or Closed Status can t be...

Страница 48: ...llowing can be changed by pressing the DOWN key Channel Open or Closed Delay the range is 0 999 seconds Status Open or Closed Status can t be changed Once a selection or selections have been made move...

Страница 49: ...hanged by pressing the DOWN key Channel Open or Closed Delay the range is 0 999 seconds Status Open or Closed Status can t be changed Once a selection or selections have been made move the cursor to t...

Страница 50: ...Delay the range is 0 999 seconds Status Open or Closed Status can t be changed Once a selection or selections have been made move the cursor to the title block by pressing the ENTER key Press the DOWN...

Страница 51: ...tions have been made move the cursor to the title block by pressing the ENTER key Press the DOWN key to view the next screen The following will be displayed values are for reference only Move the curs...

Страница 52: ...ENTER key Press the DOWN key to view the next screen The following will be displayed values are for reference only Move the cursor by pressing the ENTER key Move the cursor to change the setting The...

Страница 53: ...key to view the next screen The following will be displayed values are for reference only Move the cursor by pressing the ENTER key Move the cursor to change the setting The following can be changed...

Страница 54: ...key to view the next screen The following will be displayed values are for reference only Move the cursor by pressing the ENTER key Move the cursor to change the setting The following can be changed...

Страница 55: ...WN key to view the next screen The following will be displayed values are for reference only Move the cursor by pressing the ENTER key Move the cursor to change the setting The following can be change...

Страница 56: ...key Press the DOWN key to view the next screen The following will be displayed values are for reference only Move the cursor by pressing the ENTER key Move the cursor to change the setting The followi...

Страница 57: ...ock by pressing the ENTER key Press the DOWN key to view the next screen The following will be displayed values are for reference only Note If Enable OFF is selected the High Res Offset and Value will...

Страница 58: ...a selection or selections have been made move the cursor to the title block by pressing the ENTER key Press the DOWN key to view the next screen The following will be displayed values are for referenc...

Страница 59: ...y to view the next screen The following will be displayed values are for reference only With Enable OFF With Enable ON The Choose Name allows one of the following to be selected by moving the cursor t...

Страница 60: ...Temp CW Ret Temp CW Sply Temp Cond Ret Temp Cond Sup Temp Power Frequency Ground Amps Neutral Amps Output Amps C Output Amps B Output Amps A Input Amps C Input Amps B Input Amps A Output V B C Output...

Страница 61: ...ection or selections have been made move the cursor to the title block by pressing the ENTER key Press the DOWN key to view the next screen The following will be displayed values are for reference onl...

Страница 62: ...available DO NOT ASSIGN THE SAME CHANNEL ON MORE THAN ONE ANA LOG OUTPUT Action there are two choices DIRECT AND REVERSE Minimum the range is from 0 0vdc to 10 0vdc Maximum the range is from 0 0vdc to...

Страница 63: ...The following will be displayed values are for reference only Move the cursor by pressing the ENTER key Move the cursor to change the setting The following can be changed by pressing the DOWN key Cha...

Страница 64: ...RE THAN ONE ANA LOG OUTPUT Action there are two choices DIRECT AND REVERSE Minimum the range is from 0 0vdc to 10 0vdc Maximum the range is from 0 0vdc to 10 0vdc To return to another Input or Output...

Страница 65: ...he same primary stage compressor The delay will be increased to six 6 minutes for one 1 hour following the detection of a compressor short cycle condition even if the compressor short cycle alarm is d...

Страница 66: ...adband 0 1 F 10 Position Open Current Temperature Setpoint Deadband 0 2 F 20 Position Open Current Temperature Setpoint Deadband 0 3 F 30 Position Open Current Temperature Setpoint Deadband 0 4 F 40 P...

Страница 67: ...bove this range the Energy Saver Auxiliary Chilled Water Cooling will be inhibited for the amount of time set in Menu J Energy Saver Lockout Time and DX Direct Expansion cooling will take over After t...

Страница 68: ...sition Open 9 The dap4 will switch the unit to DX cooling for one 1 hour after every 100 hours of continuous hours of Energy Saver or Auxiliary Chilled Water Cooling ENERGY SAVER and AUXILIARY CHILLED...

Страница 69: ...t water and hot gas They are single stage Single stage operates in the follow ing manner Reheat is ON at Temperature Setpoint Temperature Deadband Reheat is OFF at Temperature Setpoint 5 Reheat will b...

Страница 70: ...DC when R A temp Temp SP Temp DB 0 8 SCR Pro band 9VDC when R A temp Temp SP Temp DB 0 9 SCR Pro band 10VDC when R A temp Temp SP Temp DB SCR Pro band When temperature rises Y4 output signal 0VDC when...

Страница 71: ...air temperature rises to the temperature setpoint Compressor short cycle time will not be violated 3 If dehumidification is programmed for No Reheat Limits it will remain ON until the humidity setpoin...

Страница 72: ...hich it will respond after each adjustment period 3 The dehumidification sequence for chilled water units is as follows Valve is OPENED to 100 at Humidity Setpoint Humidity Deadband Valve is CLOSED at...

Страница 73: ...e will open if dewpoint is increasing OR relative humidity is increasing closer to the setpoints Either high dewpoint or high relative humidity can cause the CW to open and call for dehumidification T...

Страница 74: ...3 F Open 60 if return dewpoint high_dewpoint_setpoint high_dewpoint_deadband 0 4 F Open 50 if return dewpoint high_dewpoint_setpoint high_dewpoint_deadband 0 5 F Open 40 if return dewpoint high_dewpoi...

Страница 75: ...lled by the discharge air temperature sensor iii An adjustable Minimum runtime for variable speed compressor with a range of 2 10 minutes is added the Factory Setting menu default value is 2 minutes i...

Страница 76: ...4 Factory Settings menu is programmed to Variable fixed and Control mode is set to Return Temp There is a five 5 minute delay between start to start of the same primary stage The delay will be increas...

Страница 77: ...ply is below the setpoint of the Energy saver Water Thermostat in menu B setpoint Energy Saver 2 The Energy Saver Auxiliary Chilled Water mode will operate when space temperature is between the return...

Страница 78: ...rrent Temperature Setpoint 0 5 F 50 Position Current Temperature Setpoint 0 4 F 40 Position Current Temperature Setpoint 0 3 F 30 Position Current Temperature Setpoint 0 2 F 20 Position Current Temper...

Страница 79: ...delay This step only applies to dual compressor system For instance SP 72 DB 2 and STS 0 3 the C2 compressor will on at 76 3 Compressors off cycle Fixed speed compressor C2 cycles off at Temperature S...

Страница 80: ...tings type in dap4 Factory Settings menu is programmed to Vari Fixed and Control mode is set to Supply There is a five 5 minute delay between start to start of the same primary stage The delay will be...

Страница 81: ...deadband plus Energy saver to DX change over band If the temperature rises above this range Energy Saver Auxiliary Chilled Water Cooling will be inhibited for at least 15 minutes to an hour it depend...

Страница 82: ...on at Temperature Setpoint Temperature Deadband 1 F STS DB and variable speed compressor C1 has operated at 95 for at least the C2 on delay When C2 comes on variable speed compressor C1 will drop its...

Страница 83: ...Variable speed compressor system Dehumidification cycles on If unit is not in cooling mode the variable speed compressor turns on when humidity is at Humidity Setpoint HSP Humidity Deadband HDB Compre...

Страница 84: ...nue to finish the dehumidification cycle then reverse to temperature control cooling mode Dehumidification cycles off When humidity drops Fixed speed compressor C2 NO3 will turn off when humidity Humi...

Страница 85: ...int SP 1 Deg F compressor will run at 0 0VDC If dewpoint High dewpoint SP 0 9 DegF compressor will run at 10 1V If If dewpoint High dewpoint SP 0 8 DegF compressor will run at 20 2V Etc C2 fixed speed...

Страница 86: ...essor and a fixed speed compressor Dehumidification cycles on If unit is not in cooling mode C2 fixed speed compressor turns on when humidity reaches Humidity Setpoint HSP Compressor will not violate...

Страница 87: ...on pressure alarm with manual reset can be enable in menu K alarm and limits of dap4 The default setting is disable If enabled when alarm counts match the programmed Lock out times the compressor will...

Страница 88: ...discontinued After eleven minutes the humidity alarms are enabled HUMIDITY ANTICIPATION 1 Humidity anticipation is programmable ON or OFF See Menu J Factory Settings 2 When set to ON the humidity setp...

Страница 89: ...lrm Automatic Message Audio Alarm Relay The unit will automatically re start after a power failure or reset The audio alarm will be activated and the message Power Failure Restart will be displayed on...

Страница 90: ...display module until the condition is corrected FIRESTAT TEMPERATURE ALARM 1 The firestat temperature alarm is programmable from 100 to 150 F See Menu K Alarms and Limits 2 If the return air temperatu...

Страница 91: ...the audio alarm is activated and a Low Humidity Warning message is displayed on the display module 3 The audio alarm is a warning only and will not prevent any of the unit functions form operating 4...

Страница 92: ...until the alarm condition is corrected PERSON TO CONTACT ON ALARM 1 The person to contact on alarm is programmable See Menu K Alarms and Limits It can also be disabled 2 The alarm is a warning only a...

Страница 93: ...t is required 5 The alarm will remain until the alarm condition is corrected NO WATER FLOW ALARM ACTION CHILLED WATER UNITS 1 The dap4 controller will not detect the no water flow alarm unless the chi...

Страница 94: ...odule 4 The alarm is a warning only and will not prevent any of the unit functions from operating 5 The alarm will remain until the alarm condition is corrected REHEAT INHIBITED ALARM 1 The reheat inh...

Страница 95: ...in until the alarm condition is corrected WATER UNDER FLOOR DETECTION ALARM 1 The water under floor detection alarm message is displayed when the alarm is activated the sensor has detected water 2 The...

Страница 96: ...tting when the unit stops calling for reheat or humidification WARNING IF CUSTOMER DECIDES TO USE THIS FAN SPEED CONTROL MODE FAN SPEED CONTROLLED BY BMS DATA AIRE WILL NOT BE RESPONSIBLE FOR ANY EF F...

Страница 97: ...ow menu until the dap4 receives a valid airflow value greater than the minimum allowed airflow and less than the maximum allowed airflow from a BMS This control mode requires an optional airflow measu...

Страница 98: ...s are accessible through Menu J Factory Settings Either of the following may be chosen 1 Speed Constant Const Speed 2 Speed Controlled by BMS BMS Speed 3 Static Pressure Constant Air Pressure 4 Airflo...

Страница 99: ...W menu In this mode the fan will start and operate at this con stant design airflow all the time 5 Airflow Controlled by BMS BMS Flow Optional In Airflow Controlled by BMS mode the dap4 will start and...

Страница 100: ...78 0 1 76 16 6 27 0 95 47 75 2 24 0 10 38 174 2 79 0 1 71 14 8 26 0 90 80 77 0 25 0 10 00 176 0 80 0 1 66 13 0 25 0 86 39 78 0 26 0 9 63 177 8 81 0 1 62 11 2 24 0 82 22 80 6 27 0 9 28 179 6 82 0 1 57...

Страница 101: ...101 dap4 User Manual...

Страница 102: ...N A Opt Chilled Water Temperature NTC U10 J20 5 N A NTC GND J20 6 N A Alarms Digital Inputs I O Board Pin ID ID Connector Number Unit TB Compressor 1 High Pressure Alarm ID1 J5 1 TB1 25 Compressor 1...

Страница 103: ...TB1 7 Reheat 2 NO10 J16 3 TB1 20 Reheat 3 NO11 J16 4 TB1 21 Alarm 3 NO12 J17 1 TB1 45 C12 J17 2 TB1 43 NC 12 J17 3 TB1 44 Alarm 4 NO13 J18 1 TB2 50 C13 J18 2 TB2 48 NO13 J18 3 TB2 49 Alarm 1 NO14 J21...

Страница 104: ...Simply slide the manual switches to energize the blower compressors humidification reheat and other functions The fan speed of the EC Electronically Commutated motor can be adjusted from 0 10 volts by...

Страница 105: ...additional features of Lighting control CO2 level control and Night time temperature and humidity offsets which are explained in this document 1 Two additional sensors can be installed a CO2 sensor C...

Страница 106: ...POD will appear on the main screen of dap4 Please contact the Data Aire if your dap4 controller is not set to the gPod model as required b CO2 control settings To access the CO2 level set point press...

Страница 107: ...ing a cooling offset or heating offset that cause excessive power consumption and or lead to a system short cycle A warning message will appear under such conditions For instance if cooling offset is...

Страница 108: ...will remain off An example of how CO2 is controlled let s assure that the CO2 set point is 1000ppm CO2 dead band is 25ppm Min Valve on is 10 seconds and the Valve PWM is 20 When the CO2 level falls b...

Страница 109: ...Set point offsets work as follows Normal daytime mode Cooling and Heating Temp set point Temp set point Humidify and Dehumidify set point Hum set point Temp and Hum set points are adjusted in menu B S...

Страница 110: ...com Sales dataaire com Fax 714 921 6010 Main 714 921 6011 Engineering 714 921 6022 Parts Sales Web Site www dataaire com Job Unit Information Data Aire Job Number __________________________ Serial Nu...

Страница 111: ...111 dap4 User Manual...

Страница 112: ...ange CA 92865 800 347 2473 www dataaire com sales dataaire com ISO 9001 2008 Certified Copyright 2016 Data Aire Inc A member of the CS Group of Companies Creating Products That Make Building Better da...