EN 61000-3-12, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, immunity
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61326-3-1
Energy efficiency class
2)
IE2
1) Refer to Special Conditions in the Design Guide for:
•
Derating for high ambient temperature.
•
Derating for high altitude.
2) Determined according to EN50598-2 at:
•
Rated load
•
90% rated frequency
•
Switching frequency factory setting
•
Switching pattern factory setting
9.5 Cable Specifications
Cable lengths and cross-sections
1)
Maximum motor cable length, shielded
50 m (165 ft)
Maximum motor cable length, non-shielded
75 m (250 ft)
Maximum cross-section to control terminals, flexible/rigid wire
2.5 mm
2
/14 AWG
Minimum cross-section to control terminals
0.55 mm
2
/30 AWG
Maximum STO input cable length, unshielded
20 m (65 ft)
1) For power cables, see Table 9.1 to Table 9.2.
9.6 Control Input/Output and Control Data
Digital inputs
Terminal number
18, 19, 27
1)
, 29, 32, 33
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic 0 PNP
<5 V DC
Voltage level, logic 1 PNP
>10 V DC
Voltage level, logic 0 NPN
>19 V DC
Voltage level, logic 1 NPN
<14 V DC
Maximum voltage on input
28 V DC
Pulse frequency ranges
4–32 kHz
(Duty cycle) minimum pulse width
4.5 ms
Input resistance, R
i
Approximately 4 kΩ
1) Terminals 27 can also be programmed as output.
STO inputs
1)
Terminal number
37, 38
Voltage level
0–30 V DC
Voltage level, low
<1.8 V DC
Voltage level, high
>20 V DC
Maximum voltage on input
30 V DC
Minimum input current (each pin)
6 mA
1) Refer to chapter 6 Safe Torque Off (STO) for more details about STO inputs.
Specifications
Instruction Manual
MG07A122