Figure 4.6 Line power, Motor and Grounding Connection for
Single-phase Units
130BE231.11
Figure 4.7 Line power, Motor and Grounding Connection for 3-
phase Units
4.7 AC Line Input Connection
•
Size the wiring based on the input current of the
adjustable frequency drive. For maximum wire
sizes, see
•
Comply with local and national electrical codes
for cable sizes.
Procedure
1.
Connect the AC input power cables to terminals
N and L for single-phase units (see
) or
to terminals L1, L2 and L3 for 3-phase units (see
2.
Depending on the configuration of the
equipment, connect the input power to the line
power input terminals or the input disconnect.
3.
Ground the cable in accordance with the
grounding instructions in
.
4.
When supplied from an isolated line power
source (IT line power or floating delta) or TT/TN-S
line power with a grounded leg (grounded delta),
ensure that the RFI filter screw is removed to
avoid damage to the intermediate circuit and
reduce ground capacity currents in accordance
with IEC 61800-3.
4.8 Control Wiring
4.8.1 Control Terminal Types
shows the removable adjustable frequency drive
connectors. Terminal functions and default settings are
summarized in
and
130BE212.10
1
2
3
Figure 4.8 Control Terminal Locations
Electrical Installation
Instruction Manual
MG07A122