settings, such as operating hours, serial communi-
cation selections, fault log, alarm log and other
monitoring functions.
•
Manual initialization erases all motor,
programming, localization and monitoring data
and restores factory default settings.
Recommended initialization procedure via
parameter 14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to
parameter 14-22 Operation Mode
and
press [OK].
3.
Scroll to
[2] Initialization
and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
6.
Alarm 80 is displayed.
7.
Press [Reset] to return to operation mode.
Manual initialization procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu] and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialization does not reset the following
adjustable frequency drive information:
•
Parameter 15-00 Operating hours
•
Parameter 15-03 Power Up's
•
Parameter 15-04 Over Temp's
•
Parameter 15-05 Over Volt's
5.4 Basic Programming
5.4.1 Asynchronous Motor Set-up
Enter the following motor data. The information can be
found on the motor nameplate.
1.
Parameter 1-20 Motor Power [kW]
.
2.
Parameter 1-22 Motor Voltage
.
3.
Parameter 1-23 Motor Frequency
.
4.
Parameter 1-24 Motor Current
.
5.
Parameter 1-25 Motor Nominal Speed
.
For optimum performance in VVC
+
mode, extra motor data
is required to set up the following parameters. The data is
found in the motor datasheet (this data is typically not
available on the motor nameplate). Run a complete AMA
using
parameter 1-29 Automatic Motor Adaptation (AMA)
[1]
Enable Complete AMA
or enter the parameters manually.
1.
Parameter 1-30 Stator Resistance (Rs)
.
2.
Parameter 1-31 Rotor Resistance (Rr)
.
3.
Parameter 1-33 Stator Leakage Reactance (X1)
.
4.
Parameter 1-35 Main Reactance (Xh)
.
Application-specific adjustment when running VVC
+
VVC
+
is the most robust control mode. In most situations,
it provides optimum performance without further
adjustments. Run a complete AMA for best performance.
5.4.2 PM Motor Set-up in VVC
+
Initial programming steps
1.
Set
parameter 1-10 Motor Construction
to the
following options to activate PM motor operation:
-
[1] PM, non-salient SPM
-
[2] PM, salient IPM, non Sat
-
[3] PM, salient IPM, Sat
2.
Select
[0] Open-loop
in
parameter 1-00 Configu-
ration Mode
.
NOTICE!
Encoder feedback is not supported for PM motors.
Programming motor data
After selecting PM motor in
parameter 1-10 Motor
Construction
, the PM motor-related parameters in
parameter groups
1-2* Motor Data
,
1-3* Addl. Motor Data
and
1-4* Adv. Motor Data II
are active.
The information can be found on the motor nameplate
and in the motor data sheet.
Programme the following parameters in the listed order.
1.
Parameter 1-24 Motor Current
.
2.
Parameter 1-26 Motor Cont. Rated Torque
.
3.
Parameter 1-25 Motor Nominal Speed
.
4.
Parameter 1-39 Motor Poles
.
5.
Parameter 1-30 Stator Resistance (Rs)
.
Commissioning
VLT
®
Midi Drive FC 280
28