9.2 Line Power Supply (3-phase)
Line power supply (L1, L2, L3)
Supply terminals
L1, L2, L3
Supply voltage
380–480 V: -15% (-25%)
1)
to +10%
1) The adjustable frequency drive can run at -25% input voltage with reduced performance. The maximum output power of the
adjustable frequency drive is 75% if input voltage is -25% and 85% if input voltage is -15%.
Full torque cannot be expected at AC line voltage lower than 10% below the lowest rated supply voltage of the adjustable
frequency drive.
Supply frequency
50/60 Hz
±
5%
Maximum imbalance temporary between line phases
3.0% of rated supply voltage
True power factor (
λ
)
≥
0.9 nominal at rated load
Displacement power factor (cos
ϕ
)
near unity (
>
0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
7.5 kW (10 hp)
Maximum two times/minute
Switching on input supply L1, L2, L3 (power-ups) 11–22 kW (15–30 hp)
Maximum one time/minute
The unit is suitable for use on a circuit capable of delivering less than 5000 RMS symmetrical Amperes, 480 V maximum.
9.3 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency
0–500 Hz
Output frequency in VVC
+
Mode
0–200 Hz
Switching on output
Unlimited
Ramp time
0.05–3600 s
Torque characteristics
Starting torque (constant torque)
Maximum 160% for 60 s
1)
Overload torque (constant torque)
Maximum 160% for 60 s
1)
Starting torque (variable torque)
Maximum 110% for 60 s
1)
Overload torque (variable torque)
Maximum 110% for 60 s
Starting current
Maximum 200% for 1 s
Torque rise time in VVC
+
(independent of f
sw
)
Maximum 50 ms
1) Percentage relates to the nominal torque.
9.4 Ambient Conditions
Ambient Conditions
IP class
IP20
Vibration test, all enclosure sizes
1.0 g
Relative humidity
5–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Ambient temperature (at DPWM switching mode)
- with derating
maximum 55
°
C (131 °F)
1)
- at full continuous output current with some power size
maximum 50
°
C (122 °F)
- at full continuous output current
maximum 45
°
C (113 °F)
Minimum ambient temperature during full-scale operation
0
°
C (32 °F)
Minimum ambient temperature at reduced performance
-10
°
C (14 °F)
Temperature during storage/transport
-25 to +65/70
°
C (-13 to + 149/158 °F)
Maximum altitude above sea level without derating
1000 m (3300 ft)
Maximum altitude above sea level with derating
3000 m (10000 ft)
EMC standards, emission
EN 61800-3, EN 61000-3-2, EN 61000-3-3, EN 61000-3-11,
Specifications