130BC500.10
FC 1
FC 1
FC 2
FC 2
FC 3
FC 3
PE
PE
Figure 4.1 Grounding Principle
For EMC-compliant installation
•
Establish electrical contact between the cable
shield and the adjustable frequency drive
enclosure by using metal cable connectors or by
using the clamps provided on the equipment (see
•
Use high-strand wire to reduce electrical
interference.
•
Do not use pigtails.
NOTICE!
POTENTIAL EQUALIZATION
Risk of electrical interference, when the ground potential
between the adjustable frequency drive and the control
system is different. Install equalizing cables between the
system components. Recommended cable cross-section:
16 mm
2
(5 AWG).
Electrical Installation
Instruction Manual
MG07A122