9 Specifications
9.1 Electrical Data
Adjustable frequency driver
typical shaft output [kW] (hp)
HK37
0.37 (0.5)
HK55
0.55 (0.75)
HK75
0.75 (1.0)
H1K1
1.1 (1.5)
H1K5
1.5 (2.0)
H2K2
2.2 (3.0)
H3K0
3 (4)
Enclosure IP20
K1
K1
K1
K1
K1
K1
K2
Output current
Shaft output [kW] (hp)
0.37 (0.5)
0.55 (0.75) 0.75 (1.0)
1.1 (1.5)
1.5 (2.0)
2.2 (3.0)
3 (4)
Continuous (3x380–440 V) [A]
1.2
1.7
2.2
3
3.7
5.3
7.2
Continuous (3x441–480 V) [A]
1.1
1.6
2.1
2.8
3.4
4.8
6.3
Intermittent (60 s overload) [A]
1.9
2.7
3.5
4.8
5.9
8.5
11.5
Continuous kVA (400 V AC) [kVA]
0.84
1.18
1.53
2.08
2.57
3.68
4.99
Continuous kVA (480 V AC) [kVA]
0.9
1.3
1.7
2.5
2.8
4.0
5.2
Maximum input current
Continuous (3x380–440 V) [A]
1.2
1.6
2.1
2.6
3.5
4.7
6.3
Continuous (3x441–480 V) [A]
1.0
1.2
1.8
2.0
2.9
3.9
4.3
Intermittent (60 s overload) [A]
1.9
2.6
3.4
4.2
5.6
7.5
10.1
Additional specifications
Maximum cable cross-section (line power, motor,
brake and load sharing) [mm
2
(AWG)]
4(12)
Estimated power loss at rated maximum load
[W]
1)
20.88
25.16
30.01
40.01
52.91
73.97
94.81
Weight, enclosure IP20 [kW] (hp)
2.3 (5.1)
2.3 (5.1)
2.3 (5.1)
2.3 (5.1)
2.3 (5.1)
2.5 (5.5)
3.6 (7.94)
Efficiency [%]
2)
96.2
97.0
97.2
97.4
97.4
97.6
97.5
Table 9.1 Line Power Supply 3x380–480 V AC
Specifications
VLT
®
Midi Drive FC 280
48
Danfoss A/S © 11/2015 All rights reserved.
MG07A122
9
9