Warning and Alarm Messages
There is a clear distinction between alarms and warnings. In the event of an alarm, the frequency converter will enter a fault condition. After the cause
for the alarm has been cleared, the master must acknowledge the alarm message in order to start operation of the frequency converter again. A warning,
on the other hand, may appear when a warning condition arises, then disappear when conditions return to normal without interfering with the process.
Warnings
All warnings within the frequency converter are represented by a single bit within a warning word. A warning word is always an action parameter. Bit
status FALSE [0] means no warning, while bit status TRUE [1] means warning. Each bit status has a corresponding text string message. In addition to
the warning word message the master will also be notified via a change in the status word.
Alarms
Following an alarm message the frequency converter will enter a fault condition. Only after the fault has been rectified and the master has acknowledged
the alarm message by a bit in the Control Word, can the VLT resume operation. All alarms within the VLT are represented by a single bit within an alarm
word. An alarm word is always an action parameter. Bit status FALSE [0] means no alarm, while bit status TRUE [1] means alarm. In CIP, Alarms are
divided in to two categories:
-
Major Recoverable Faults
-
Major Unrecoverable Faults
Please refer to the following sections for a classification of the specific faults.
Bit (Hex)
Alarm word (Par. 16-90)
CIP Classification
00000001
Brake check
-
00000002
Power card over temperature
MAR
00000004
Earth fault
MAU
00000008
Ctrl. card over temperature
-
00000010
Control word timeout
MAR
00000020
Torque limit
MAU
00000040
Over current
MAR
00000080
Motor thermistor over temp.
MAR
00000100
Motor ETR over temperature
MAR
00000200
Inverter overloaded
MAR
00000400
DC link under voltage
MAR
00000800
DC link over voltage
MAR
00001000
Short circuit
MAU
00002000
Inrush fault
MAR
00004000
Mains phase loss
MAU
00008000
AMA not OK
MAR
00010000
Live zero error
MAR
00020000
Internal fault
MAU
00040000
Brake overload
MAU
00080000
Motor phase U is missing
MAU
00100000
Motor phase V is missing
MAU
00200000
Motor phase W is missing
MAU
00400000
Fieldbus fault
MAR
00800000
24V supply fault
MAU
01000000
Mains failure
MAR
02000000
1.8V supply fault
MAU
04000000
Brake resistor short circuit
MAR
08000000
Brake chopper fault
MAR
10000000
Option change
-
20000000
Drive initialized
-
40000000
Safe Stop
MAR
80000000
Mech. Brake low
-
MAR = Major Recoverable Fault
MAU = Major Unrecoverable Fault
7 Troubleshooting
MCA 121 EtherNet/IP
46
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
7
Содержание VLT MCA 121 EtherNet/IP
Страница 14: ...4 How to Configure MCA 121 EtherNet IP 14 MG 90 J2 02 VLT is a registered Danfoss trademark 4...
Страница 20: ...5 How to Control MCA 121 EtherNet IP 20 MG 90 J2 02 VLT is a registered Danfoss trademark 5...
Страница 50: ...8 Appendix MCA 121 EtherNet IP 50 MG 90 J2 02 VLT is a registered Danfoss trademark 8...