5.2 Danfoss FC Control Profile
5.2.1 Danfoss FC Control Profile
Control Word according to FC ProfileDrive Profile. Instances 100, 101,
103/150, 151, 153
→
Illustration 5.1: (par.8-10
= FC profile)
Bit
Bit value = 0
Bit value = 1
00
Reference value
External selection LSB
01
Reference value
External selection MSB
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output frequency
Use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 04 active
13
Parameter set-up
Selection LSB
14
Parameter set-up
Selection MSB
15
No function
Reverse
Explanation of Control Bits
Bits 00/01
Bits 00 and 01 are used to choose between the four reference values,
which are pre-programmed in par. 3-10
Preset Reference
according to
the following table:
Programmed
ref. value
Parameter
Bit 01
Bit 00
1
3-10 [0]
0
0
2
3-10 [1]
0
1
3
3-10 [2]
1
0
4
3-10 [3]
1
1
NB!
In par. 8-56
Preset Reference Select
select a selection
is made to define how Bit 00/01 gates with the corre-
sponding function on the digital inputs.
Bit 02, DC brake:
Bit 02 = ‘0’ leads to DC braking and stop. Braking current and duration
are set in par. 2-01
DC Brake Current
and par. 2-02
DC Braking Time
. Bit
02 = ‘1’ leads to ramping, par. 3-41
Ramp 1 Ramp up Time
Bit 03, Coasting:
Bit 03 = ‘0’ causes the frequency converter to immediately "let go" of the
motor (the output transistors are "shut off"), so that it coasts to a stand-
still.
Bit 03 = ‘1’ enables the frequency converter to start the motor if the other
starting conditions have been fulfilled.
NB!
In par. 8-50
Coasting Select
a selection is made to de-
fine how Bit 03 gates with the corresponding function
on a digital input.
Bit 04, Quick stop:
Bit 04 = ‘0’ causes a stop, in which the motor speed is ramped down to
stop via par. 3-81
Quick Stop Ramp Time
.
Bit 05, Hold output frequency:
Bit 05 = ‘0’ causes the present output frequency (in Hz) to freeze. The
frozen output frequency can then be changed only by means of the digital
inputs (par. 5-10
Terminal 18 Digital Input
to par. 5-15
Terminal 33 Digital
Input
) programmed to
Speed up
and
Speed down
.
NB!
If Freeze output is active, the frequency converter can
only be stopped by the following:
•
Bit 03 Coasting stop
•
Bit 02 DC braking
•
Digital input (par. 5-10
Terminal 18 Digital
Input
to par. 5-15
Terminal 33 Digital Input
)
programmed to
DC braking
,
Coasting stop
or
Reset and coasting stop
MCA 121 EtherNet/IP
5 How to Control
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
25
5
Содержание VLT MCA 121 EtherNet/IP
Страница 14: ...4 How to Configure MCA 121 EtherNet IP 14 MG 90 J2 02 VLT is a registered Danfoss trademark 4...
Страница 20: ...5 How to Control MCA 121 EtherNet IP 20 MG 90 J2 02 VLT is a registered Danfoss trademark 5...
Страница 50: ...8 Appendix MCA 121 EtherNet IP 50 MG 90 J2 02 VLT is a registered Danfoss trademark 8...