Bit 06, Ramp stop/start:
Bit 06 = ‘0’ causes a stop, in which the motor speed is ramped down to
stop via the selected
ramp down
parameter. Bit 06 = ‘1’ permits the fre-
quency converter to start the motor, if the other starting conditions have
been fulfilled.
NB!
In par. 8-53
Start Select
Start select a selection is made
to define how Bit 06 Ramp stop/start gates with the
corresponding function on a digital input.
Bit 07, Reset:
Bit 07 = ‘0’ no reset. Bit 07 = ‘1’ resets a trip. Reset is activated on the
leading edge of the signal, i.e. when changing from logic ‘0’ to logic ‘1’.
Bit 08, Jog:
Bit 08 = ‘1’ causes the output frequency to be determined by
par. 3-19
Jog Speed [RPM]
.
Bit 09, Selection of ramp 1/2:
Bit 09 = ‘0’ means that ramp 1 is active (par. 3-40
Ramp 1 Type
to
par. 3-47
Ramp 1 S-ramp Ratio at Decel. Start
). Bit 09 = ‘1’ means that
ramp 2 (par. 3-50
Ramp 2 Type
to par. 3-57
Ramp 2 S-ramp Ratio at
Decel. Start
) is active.
Bit 10, Data not valid/Data valid:
This bit tells the frequency converter whether the control word is to be
used or ignored. Bit 10 = ‘0’ causes the control word to be ignored, Bit
10 = ‘1’ causes the control word to be used. The control word is always
contained in the telegram, regardless of which type of telegram is used,
so this function is useful for ‘turning off’ the control word when not re-
quired for updating or reading parameters.
Bit 11, Relay 01:
Bit 11 = ‘0’ Relay not activated. Bit 11 = ‘1’ Relay 01 activated, provided
Control word bit 11
has been chosen in par. 5-40
Function Relay
.
Bit 12, Relay 02:
Bit 12 = ‘0’ Relay 02 has not been activated. Bit 12 = ‘1’ Relay 02 has
been activated, provided
Control word bit 12
has been chosen in
par. 5-40
Function Relay
.
Bit 13/14, Selection of set-up:
Bits 13 and 14 are used to select one of four menu set-ups according to
the following table:
Set-up
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
The function is only possible when
Multi-Set-ups
is selected in
par. 0-10
Active Set-up
.
NB!
In par. 8-55
Set-up Select
a selection is made to define
how Bit 13/14 gates with the corresponding function
on the digital inputs.
Bit 15 Reverse:
Bit 15 = ‘0’ causes no reversing. Bit 15 = ‘1’ causes reversing. Note: In
the factory setting reversing is set to
digital
. Bit 15 causes reversing only when
Ser. communication
,
Logic AND
or
Logic OR
is selected.
5.2.2 Status Word according to FC ProfileDrive Profile (STW)
→
Illustration 5.2: (par.8-10
Bit
Bit value = 0
Bit value = 1
00
Control not ready
Control ready
01
Drive not ready
Drive ready
02
Coasting
Enable
03
No error
Trip
04
No error
Error (no trip)
05
Reserved
-
06
No error
Trip lock
07
No warning
Warning
08
Speed
≠
reference
Speed = reference
09
Local operation
Bus control
10
Out of frequency limit
Frequency limit ok
11
No operation
In operation
12
Drive ok
Stopped, auto start
13
Voltage ok
Voltage exceeded
14
Torque ok
Torque exceeded
15
Thermal ok
Thermal exceeded
5 How to Control
MCA 121 EtherNet/IP
26
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
5
Содержание VLT MCA 121 EtherNet/IP
Страница 14: ...4 How to Configure MCA 121 EtherNet IP 14 MG 90 J2 02 VLT is a registered Danfoss trademark 4...
Страница 20: ...5 How to Control MCA 121 EtherNet IP 20 MG 90 J2 02 VLT is a registered Danfoss trademark 5...
Страница 50: ...8 Appendix MCA 121 EtherNet IP 50 MG 90 J2 02 VLT is a registered Danfoss trademark 8...