4.1.3 Configuring the Scanner
EDS file
Danfoss provides a generic English EDS (Electronic Data Sheet) file covering all voltage and power sizes, for off-line configuration.
The EDS file can be downloaded from:
http://www.danfoss.com/BusinessAreas/DrivesSolutions/Softwaredownload/DDFieldbus_Setup_Files.htm
NB!
The current version of the major EtherNet/IP configuration tools does not support EDS-files for EtherNet/IP devices.
Configuring a Rockwell Master
For configuring a FC 200/FC 300 with MCA121 for operation with a Rockwell (Allen-Bradley) Scanner via EtherNet/IP, the FC 200/FC 300 must be added
as a
Generic Ethernet Module
.
Under the
General
-tab, enter information about: Name of device, IP Address, Assembly Instance and Data size
NB!
Under
Configuration
in the Connection Parameters a “4” must be entered as Assembly Instance.
NB!
Please note that the example shows a 20/70 assembly instance connection. This requires par. 8-10
Control Profile
to be set to: ODVA.
Other supported connections are shown in section:
I/O Assembly Instanced
.
Under the
Connection
-tab, enter information about: RII and fault conditions.
MCA 121 EtherNet/IP
4 How to Configure
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
17
4