
5.5. 16-** Data readouts
5.5.1. 16-6* Inputs and Outputs
Parameters for reporting the digital and analog IO ports.
16-60 Digital Input
Range:
Function:
0
[0 - 63]
View the signal states from the active digital inputs. Example: Input 18 corresponds to bit no. 5, ‘0’
= no signal, ‘1’ = connected signal. Bit 6 works in the opposite way, on = '0', off = '1' (safe stop
input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
130BA894.10
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
DI T-33
DI T-32
DI T-29
DI T-27
DI T-19
DI T-18
DI T-37
DI X30/4
DI X30/3
DI X30/2
DI X46/13
DI X46/11
DI X46/9
DI X46/7
DI X46/5
DI X46/3
DI X46/1
FC 300 Extended Relay Card Operating In-
structions
5. Parameter Set-up
MI.33.G2.02 - VLT
®
is a registered Danfoss trademark
23
5