5-41 On Delay, Relay
Enter the delay of the relay cut-in time. See par. 5-40.
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay 6 [5], Relay 6 [5], Relay
7 [6], Relay 8 [7], Relay 9 [8])
0.01s*
[0.01 - 600.00 s ]
5-42 Off Delay, Relay
Enter the delay of the relay cut-out time. See par. 5-40.
Array [8]
(Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay 6 [5], Relay 6 [5], Relay
7 [6], Relay 8 [7], Relay 9 [8])
0.01s*
[0.01 - 600.00 s.]
If the Selected Event condition changes before the on- or off delay timer expires, the relay output
is unaffected.
5.3. 6-** Analog Outputs
5.3.1. 6-7* Analog Output 3
Parameters for configuring the scaling and limits for analog output 3, Terminal X45/1 and X45/2. Analog outputs are current outputs: 0/4 – 20 mA.
Resolution on analog output is 11 bit.
6-70 Terminal X45/1 Output
Option:
Function:
Select the function of Terminal X45/1 as an analog current output.
[0]
No operation
When no signal on the analog output.
[52]
MCO 305 0-20 mA
[53]
MCO 305 4-20 mA
FC 300 Extended Relay Card Operating In-
structions
5. Parameter Set-up
MI.33.G2.02 - VLT
®
is a registered Danfoss trademark
19