5-26 Terminal X46/13 Digital Input
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 113 is installed in the frequency converter.
Follow the function stated in 5-1*
5.2.2. 5-3* Digital Outputs
Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are common for terminals 27 and 29. Set the
I/O function for terminal 27 in par. E-51 Terminal
27 Mode
, and set the I/O function for terminal 29 in par. E-52 Terminal
29 Mode
. These parameters
cannot be adjusted while the motor is running.
[0]
No operation
Default for all digital outputs and relay outputs
[1]
Control ready
The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for operation and applies a supply signal on the control board.
[3]
Drive ready / remote control
The frequency converter is ready for operation and is in Auto On mode.
[4]
Enable / no warning
Ready for operation. No start or stop command is been given (start/disable). There are no warnings.
[5]
VLT running
Motor is running.
[6]
Running / no warning
Output speed is higher than the speed set in par. H-81 Min
Speed for Function at Stop [RPM]
. The
motor is running and there are no warnings.
[7]
Run in range / no warning
Motor is running within the programmed current and speed ranges set in par. H-70 Warning
Current
Low
to par. H-73 Warning
Speed High
. There are no warnings.
[8]
Run on reference / no warning
Motor runs at reference speed.
[9]
Alarm
An alarm activates the output. There are no warnings.
[10]
Alarm or warning
An alarm or a warning activates the output.
[11]
At torque limit
The torque limit set in par. F-40 Torque
Limiter (Driving)
or par. 1-17 has been exceeded.
[12]
Out of current range
The motor current is outside the range set in par. F-43 Current
Limit
.
[13]
Below current, low
Motor current is lower than set in par. H-70 Warning
Current Low
.
[14]
Above current, high
Motor current is higher than set in par. H-71 Warning
Current High
.
[15]
Out of range
Output frequency is outside the frequency range set in par. H-70 Warning
Current Low
and par.
H-71 Warning
Current High
.
[16]
Below speed, low
Output speed is lower than the setting in par. H-72 Warning
Speed Low
.
[17]
Above speed, high
Output speed is higher than the setting in par. H-73 Warning
Speed High
.
[18]
Out of feedback range
Feedback is outside the range set in par. H-76 Warning
Feedback Low
and par. H-77 Warn-
ing
Feedback High
.
[19]
Below feedback low
Feedback is below the limit set in par. H-76 Warning
Feedback Low
.
[20]
Above feedback high
Feedback is above the limit set in par. H-77 Warning
Feedback High
.
[21]
Thermal warning
The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency
converter, the brake resistor, or the thermistor.
[22]
Ready, no thermal warning
Frequency converter is ready for operation and there is no over-temperature warning.
[23]
Remote, ready, no thermal warning Frequency converter is ready for operation and is in Auto On mode. There is no over-temperature
warning.
[24]
Ready, no over-/ under voltage
Frequency converter is ready for operation and the mains voltage is within the specified voltage
range (see
General Specifications
section).
[25]
Reverse
Reversing. Logic ‘1’
when CW rotation of the motor. Logic ‘0’ when CCW rotation of the motor. If
the motor is not rotating the output will follow the reference.
[26]
Bus OK
Active communication (no time-out) via the serial communication port.
[27]
Torque limit and stop
Use in performing a coasting stop and in torque limit condition. If the frequency converter has
received a stop signal and is at the torque limit, the signal is Logic ‘0’.
[28]
Brake, no brake warning
Brake is active and there are no warnings.
[29]
Brake ready, no fault
Brake is ready for operation and there are no faults.
FC 300 Extended Relay Card Operating In-
structions
5. Parameter Set-up
MI.33.G2.02 - VLT
®
is a registered Danfoss trademark
15