Preset ramp bit
1
0
Ramp 1
0
0
Ramp 2
0
1
Ramp 3
1
0
Ramp 4
1
1
[36]
Mains failure inverse
Activates par. SP-10 Line
failure
. Mains failure inverse is active in the Logic .0. situation.
[41]
Latched Precise Stop inverse
Sends a latched stop signal when the precise stop function is activated in par. H-83 Precise
Stop
Function
. The Latched Precise stop inverse function is available for terminals 18 or 19.
[55]
DigiPot Increase
INCREASE signal to the Digital Potentiometer function described in parameter group 3-9*
[56]
DigiPot Decrease
DECREASE signal to the Digital Potentiometer function described in parameter group 3-9*
[57]
DigiPot Clear
Clears the Digital Potentiometer reference described in parameter group 3-9*
[60]
Counter A
(Terminal 29 or 33 only) Input for increment counting in the SLC counter.
[61]
Counter A
(Terminal 29 or 33 only) Input for decrement counting in the SLC counter.
[62]
Reset Counter A
Input for reset of counter A.
[63]
Counter B
(Terminal 29 or 33 only) Input for increment counting in the SLC counter.
[64]
Counter B
(Terminal 29 or 33 only) Input for decrement counting in the SLC counter.
[65]
Reset Counter B
Input for reset of counter B.
[70]
Mech. Brake Feedback
Brake feedback for hoisting applications
[71]
Mech. Brake Feedback inv.
Inverted brake feedback for hoisting applications
[80]
PTC Card 1
All Digital Inputs can be set to PTC Card 1 [80]. However, only one Digital Input must be set to this
choice.
5-20 Terminal X46/1 Digital Input (MCB 113)
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 113 is installed in the frequency converter.
Follow the function stated in 5-1*
5-21 Terminal X46/3 Digital Input
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 113 is installed in the frequency converter.
Follow the function stated in 5-1*
5-22 Terminal X46/5 Digital Input
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 113 is installed in the frequency converter.
Follow the function stated in 5-1*
5-23 Terminal X46/7 Digital Input
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 113 is installed in the frequency converter.
Follow the function stated in 5-1*
5-24 Terminal X46/9 Digital Input
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 113 is installed in the frequency converter.
Follow the function stated in 5-1*
5-25 Terminal X46/11 Digital Input
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 113 is installed in the frequency converter.
Follow the function stated in 5-1*
5. Parameter Set-up
FC 300 Extended Relay Card Operating In-
structions
14
MI.33.G2.02 - VLT
®
is a registered Danfoss trademark
5