[100]
Output frequency 0-20 mA
0 Hz = 0 mA; 100 Hz = 20 mA.
[101]
Reference 0-20 mA
Par. 3-00 [Min - Max] 0% = 0 mA; 100% = 20 mA
Par. 3-00 [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
[102]
Feedback
[103]
Motor current 0-20 mA
Value is taken from par. 16-37. Inverter max. current (160% current) is equal to 20 mA.
Example: Inverter norm current (11 kW) = 24 A. 160 % = 38.4 A. Motor norm current = 22 A Read-
out 11.46 mA.
20
mA x 22 A
38.4
A
= 11.46
mA
In case the norm motor current is equal to 20 mA, the output setting of par. 6-52 is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
[104]
Torque rel to lim 0-20 mA
The torque setting is related to setting in par. 4-16
[105]
Torque rel to rated motor torque
0-20 mA
The torque is related to the motor torque setting.
[106]
Power 0-20 mA
Taken from par. 1-20.
[107]
Speed 0-20 mA
Taken from par. 3-03. 20 mA = value in par. 3-03
[108]
Torque ref. 0-20 mA
Torque reference related to 160% torque.
[109]
Max Out Freq 0-20 mA
In relation to par. 4-19.
[130]
Output freq. 4-20 mA
0 Hz = 4 mA, 100 Hz = 20 mA
[131]
Reference 4-20 mA
Par. 3-00 [Min-Max] 0% = 4 mA; 100% = 20 mA
Par. 3-00 [-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
[132]
Feedback 4-20 mA
[133]
Motor cur. 4-20 mA
Value is taken from par. 16-37. Inverter max. current (160% current) is equal to 20 mA.
Example: Inverter norm current (11 kW) = 24 A. 160 % = 38.4 A. Motor norm current = 22 A Read-
out 11.46 mA.
16
mA x 22 A
38.4
A
= 9.17
mA
In case the norm motor current is equal to 20 mA, the output setting of par. 6-52 is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
[134]
Torque % lim. 4-20 mA
The torque setting is related to setting in par. 4-16.
[135]
Torque % nom 4-20 mA
The torque setting is related to the motor torque setting.
[136]
Power 4-20 mA
Taken from par. 1-20
[137]
Speed 4-20 mA
Taken from par. 3-03. 20 mA = Value in par. 3-03.
[138]
Torque 4-20 mA
Torque reference related to 160% torque.
[139]
Bus ctrl. 0-20 mA
An output value set from fieldbus process data. The output will work independently of internal
functions in the frequency converter.
[140]
Bus ctrl. 4-20 mA
An output value set from fieldbus process data. The output will work independently of internal
functions in the frequency converter.
[141]
Bus ctrl. 0-20 mA, timeout
Par. 4-54 defines the behaviour of the analog output in case of bus time-out.
[142]
Bus ctrl. 4-20 mA, timeout
Par. 4-54 defines the behaviour of the analog output in case of bus time-out.
[150]
Max Out Freq 4-20 mA
In relation to par. 4-19.
5. Parameter Set-up
FC 300 Extended Relay Card Operating In-
structions
20