Bit 05, not used
Bit 05 is not used in the status word.
Bit 06, no error/triplock
Bit 06 = 0, the frequency converter is not in fault mode.
Bit 06 = 1, the frequency converter is tripped and locked.
Bit 07, no warning/warning
Bit 07 = 0, there are no warnings.
Bit 07 = 1, a warning has occurred.
Bit 08, speed ≠ reference/speed = reference
Bit 08 = 0, the motor runs, but the present speed is
different from the preset speed reference. It could, for
example, be the case while the speed ramps up/down
during start/stop.
Bit 08 = 1, the present motor speed matches the preset
speed reference.
Bit 09, local operation/bus control
Bit 09 = 0, [Stop/Reset] is pressed on the LCP, or
[2] Local
is
selected in
parameter 3-13 Reference Site
. It is not possible
to control the frequency converter via serial communi-
cation.
Bit 09 = 1, it is possible to control the frequency converter
via the fieldbus/serial communication.
Bit 10, out of frequency limit
Bit 10 = 0, the output frequency has reached the value in
parameter 4-11 Motor Speed Low Limit [RPM]
or
parameter 4-13 Motor Speed High Limit [RPM]
.
Bit 10 = 1, the output frequency is within the defined
limits.
Bit 11, no operation/in operation
Bit 11 = 0, the motor does not run.
Bit 11 = 1, the frequency converter has a start signal or the
output frequency is higher than 0 Hz.
Bit 12, frequency converter OK/stopped, auto-start
Bit 12 = 0, there is no temporary overtemperature in the
frequency converter.
Bit 12 = 1, the frequency converter has stopped because of
overtemperature, but it has not tripped and resumes
operation once the temperature is within the defined
limits.
Bit 13, voltage OK/limit exceeded
Bit 13 = 0, there are no voltage warnings.
Bit 13 = 1, the DC voltage in the frequency converter’s DC
link is too low or too high.
Bit 14, torque OK/limit exceeded
Bit 14 = 0, the motor current is lower than the torque limit
selected in
parameter 4-16 Torque Limit Motor Mode
or
parameter 4-17 Torque Limit Generator Mode
.
Bit 14 = 1, the torque limits in
parameter 4-16 Torque Limit
Motor Mode
and
parameter 4-17 Torque Limit Generator
Mode
are exceeded.
Bit 15, thermal OK/limit exceeded
Bit 15 = 0, the timers for motor thermal protection and
frequency converter thermal protection have not exceeded
100%.
Bit 15 = 1, 1 of the limits has exceeded 100%.
Control
PROFINET
20