If
[3] Logic OR
is selected, activation of 1 signal activates
the function.
Terminal
Bits 00/01, 13/14
Function
Msb
Lsb
Msb
Lsb
Preset reference set-
up number
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
2
0
1
0
1
2
0
1
1
0
4
0
1
1
1
4
1
0
0
0
3
1
0
0
1
4
1
0
1
0
3
1
0
1
1
4
1
1
0
0
4
1
1
0
1
4
1
1
1
0
4
Table 8.12 [3] Logic OR
8.2 Warnings and Alarms
PROFINET alarm words and warning words are shown on
the display in hex format. If there is more than 1 warning
or alarm, a sum of all warnings or alarms is shown. Alarm
word, warning word, and PROFINET warning word can also
be shown using the serial bus in
parameter 16-90 Alarm
Word
,
parameter 16-92 Warning Word
, and
parameter 9-53 Profibus Warning Word
.
Bit (hex)
Unit
diagnose
bit
Alarm word
(
parameter 16-90 Alarm
Word
)
Alarm
number
00000001
48
Brake check
28
00000002
49
Power card overtem-
perature
69
00000004
50
Earth fault
14
00000008
51
Control card overtem-
perature
65
00000010
52
Control word timeout
18
00000020
53
Overcurrent
13
00000040
54
Torque limit
12
00000080
55
Motor thermistor overtem-
perature
11
00000100
40
Motor ETR overtem-
perature
10
00000200
41
Inverter overloaded
9
00000400
42
DC-link undervoltage
8
00000800
43
DC-link overvoltage
7
00001000
44
Short circuit
16
00004000
46
Mains phase loss
4
00008000
47
AMA not OK
52
00010000
32
Live zero error
2
00020000
33
Internal fault
38
00040000
34
Brake overload
26
00080000
35
Motor phase U is missing
30
00100000
36
Motor phase V is missing
31
00200000
37
Motor phase W is missing
32
00400000
38
Fieldbus comm. fault
34
00800000
39
24 V supply fault
47
01000000
24
Mains failure
36
04000000
26
Brake resistor short circuit
25
08000000
27
Brake chopper fault
27
10000000
28
Option change
67
20000000
29
Frequency converter
initialization
80
80000000
31
Mechanical brake low
63
Table 8.13 Parameter 16-90 Alarm Word
Troubleshooting
PROFINET
50