4.2 Process Data
Use the process data part of the PPO to control and
monitor the frequency converter via the PROFINET.
4.2.1 PCD
Control word (CTW) according to PROFIdrive profile:
Control words consist of 16 bits. The meaning of each bit
is explained in and . The following bit pattern sets all
necessary start commands:
0000 0100 0111 1111 = 047F hex.
1)
0000 0100 0111 1110 = 047E hex.
1)
0000 0100 0111 1111 = 047F hex.
1) For restart after power-up:
•
Set bits 1 and 2 of the CTW to 1.
•
Toggle bit 0 0–1.
These values are for bytes 9 and 10 in
.
Quick stop: 0000 0100 0110 1111 = 046F hex.
Stop: 0000 0100 0011 1111 = 043F hex.
4.2.2 MRV
MRV is the speed reference with data format
Standardized
value
. 0 hex = 0% and 4000 hex = 100%.
In the example, 2000 hex is used corresponding to 50% of
the maximum frequency in
parameter 3-03 Maximum
Reference
. See the values for bytes 11 and 12 in
.
The whole PPO therefore has the following values in hex:
Byte
Value
PCD
CTW
9
04
CTW
10
7F
MRV
11
20
MVR
12
00
Table 4.1 Request Example: PPO Values in Hex
The process data within the PCD part acts immediately
upon the frequency converter and can be updated from
the master as quickly as possible.
shows a positive response to the request example
from
.
Byte
Value
PCD
STW
9
0F
STW
10
07
MAV
11
20
MAR
12
00
Table 4.2 Response Example: Positive Response
The PCD part responds according to the state and parame-
terization of the frequency converter.
PCD part response:
•
STW: 0F07 hex means that the motor is running
and there are no warnings or faults.
•
MAV: 2000 hex indicates that the output
frequency is 50% of the maximum reference.
shows a negative response to the request
example from
.
Byte
Value
PCD
STW
9
0F
STW
10
07
MAV
11
20
MAR
12
00
Table 4.3 Response Example: Negative Response
4.2.3 Process Control Data
Process control data (PCD) is the process data sent from
the PLC to the frequency converter.
Master/slave
1
2
3
.......
10
CTW
MRV
PCD
.......
PCD
PCD write
Table 4.4 Process Control Data
PCD 1 contains a 16-bit control word, and each bit controls
a specific function of the frequency converter. See
.
PCD 2 contains a 16-bit speed setpoint in percentage
format. See
chapter 4.2.5 Reference Handling
The settings in
parameter 9-15 PCD Write Configuration
and
parameter 9-16 PCD Read Configuration
define the content
of PCD 3 to PCD 10.
Control
Programming Guide
MG06G102