Numb
er
Description
Warning
Alarm
Trip lock
Cause
13
Overcurrent
X
X
X
Inverter peak current limit is exceeded. For J1–J6 units, if
this alarm occurs on power-up, check whether power
cables are mistakenly connected to the motor terminals.
14
Earth fault
–
X
X
Discharge from output phases to ground.
16
Short circuit
–
X
X
Short circuit in motor or on motor terminals. For J7 units,
if this alarm occurs on power-up, check whether power
cables are mistakenly connected to the motor terminals.
17
Control word timeout
X
X
–
No communication to frequency converter.
18
Start failed
–
X
–
–
25
Brake resistor short-circuited
–
X
X
Brake resistor is short-circuited, thus the brake function is
disconnected.
26
Brake overload
X
X
–
The power transmitted to the brake resistor over the last
120 s exceeds the limit. Possible corrections: Decrease
brake energy via lower speed or longer ramp time.
27
Brake IGBT/Brake chopper short-
circuited
–
X
X
Brake transistor is short-circuited, thus brake function is
disconnected.
28
Brake check
–
X
–
Brake resistor is not connected/working.
30
U phase loss
–
X
X
Motor phase U is missing. Check the phase.
31
V phase loss
–
X
X
Motor phase V is missing. Check the phase.
32
W phase loss
–
X
X
Motor phase W is missing. Check the phase.
34
Fieldbus fault
X
X
–
PROFIBUS communication issues have occurred.
35
Option fault
–
X
–
Fieldbus or option B detects internal faults.
36
Mains failure
X
X
–
This warning/alarm is only active if the supply voltage to
the frequency converter is lost and
parameter 14-10 Mains
Failure
is NOT set to
[0] No Function
.
38
Internal fault
–
X
X
Contact the local Danfoss supplier.
40
Overload T27
X
–
–
Check the load connected to terminal 27 or remove
short-circuit connection.
41
Overload T29
X
–
–
Check the load connected to terminal 29 or remove
short-circuit connection.
46
Gate drive voltage fault
–
X
X
–
47
24 V supply low
X
X
X
24 V DC may be overloaded.
50
AMA calibration
–
X
–
–
51
AMA check U
nom
and I
nom
–
X
–
Wrong setting for motor voltage and/or motor current.
52
AMA low I
nom
–
X
–
Motor current is too low. Check the settings.
53
AMA big motor
–
X
–
The power size of the motor is too large for the AMA to
operate.
54
AMA small motor
–
X
–
The power size of the motor is too small for the AMA to
operate.
55
AMA parameter range
–
X
–
The parameter values of the motor are outside of the
acceptable range. AMA does not run.
56
AMA interrupt
–
X
–
The AMA is interrupted.
57
AMA timeout
–
X
–
–
58
AMA internal
–
X
–
Contact Danfoss.
59
Current limit
X
X
–
Frequency converter overload.
60
External Interlock
–
X
–
–
61
Encoder loss
X
X
–
–
63
Mechanical brake low
–
X
–
Actual motor current has not exceeded release brake
current within start delay time window.
65
Control card temp
X
X
X
The cutout temperature of the control card is 80
°
C
(176
°
F).
69
Power card temp
X
X
X
–
Troubleshooting
Programming Guide
MG06G102
Danfoss A/S © 04/2017 All rights reserved.