130BE937.10
Illustration 3.4 Open the Properties for the Inserted
Frequency Converter to Enter the Device Name
NOTICE
The name must match the name in
parameter 12-08 Host
Name
. If the check mark
Assign IP address via the IO
controller
is set, the controller downloads the IP address
to the IO device with the corresponding device name.
The IP address is stored in the non-volatile memory of
the frequency converter.
130BE938.10
Illustration 3.5 Set Up the Hardware and Add a PROFINET
Master System
The next step is to set up the peripheral input and output
data. Data set-up in the peripheral area is transmitted
cyclically via telegrams/PPO types. In the example below, a
PPO type 6 is dragged and dropped to slot 1.
130BE939.10
Illustration 3.6 Set up the Peripheral Input and Output Data
The configuration tool automatically assigns addresses in
the peripheral address area. In this example, the input and
output area have the following configuration:
PPO type 6
PCD word
number
0
1
2
3
Input
address
256–257 258–259
260–261
262–263
Set-up
STW
MAV
Parameter 9-16
PCD Read
Configuration
Parameter 9-16
PCD Read
Configuration
Table 3.2 PCD Read (Frequency Converter to PLC)
PCD word
number
0
1
2
3
Output
address
256–257 258–259
260–261
262–263
Set-up
CTW
MRV
Parameter 9-15
PCD Write
Configuration
Parameter 9-15
PCD Write
Configuration
Table 3.3 PCD Write (PLC to Frequency Converter)
Assign the PCDs via
parameter 9-16 PCD Read Configuration
for inputs and
parameter 9-15 PCD Write Configuration
for
outputs.
Download the configuration file to the PLC. The PROFINET
system starts the data exchange when the PLC is set to
Run mode.
Configuration
PROFINET
8
Danfoss A/S © 04/2017 All rights reserved.
MG06G102
3