4.4 PROFIdrive Control Profile
This section describes the functionality of the control word
and status word in the PROFIdrive profile.
4.4.1 Control Word According to
PROFIdrive Profile (CTW)
The control word is used to send commands from a master
(for example a PC) to a slave.
Bit
Bit = 0
Bit = 1
00
OFF 1
ON 1
01
OFF 2
ON 2
02
OFF 3
ON 3
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold frequency output
Use ramp
06
Ramp stop
Start
07
No function
Reset
08
Jog 1 OFF
Jog 1 ON
09
Jog 2 OFF
Jog 2 ON
10
Data invalid
Data valid
11
No function
Slow down
12
No function
Catch up
13
Parameter set-up
Selection lsb
14
No function
No function
15
Forward
Reverse
Table 4.8 Control Word Bits
Explanation of the control bits
Bit 00, OFF 1/ON 1
Normal ramp stops using the ramp times of the actual
selected ramp.
Bit 00 = 0 stops and activates the output relay 1 or 2 if the
output frequency is 0 Hz, and if
[31] Relay 123
is selected
in
parameter 5-40 Function Relay
.
When bit 0 = 1, the frequency converter is in state 1,
switching on inhibited.
Refer to
.
Bit 01, OFF 2/ON 2
Coast stop.
Bit 01 = 0 coast stops and activates the output relay 1 or 2
if the output frequency is 0 Hz, and if
[31] Relay 123
is
selected in
parameter 5-40 Function Relay
.
When bit 01 = 1, the frequency converter is in state 1,
switching on inhibited. Refer to
.
Bit 02, OFF 3/ON 3
Quick stop using the ramp time of
parameter 3-81 Quick
Stop Ramp Time
.
Bit 02 = 0 quick stops and activates the output relay 1 or 2
if the output frequency is 0 Hz, and if
[31] Relay 123
is
selected in
parameter 5-40 Function Relay
.
When bit 02 = 1, the frequency converter is in state 1,
switching on inhibited.
Refer to
Bit 03, coasting/no coasting
Bit 03 = 0 leads to a coast stop.
When bit 03 = 1, if the other start conditions are fulfilled,
the frequency converter can start.
NOTICE
The selection in
parameter 8-50 Coasting Select
determines how bit 03 is linked with the corresponding
function of the digital inputs.
Bit 04, quick stop/ramp
Quick stop using the ramp time of
parameter 3-81 Quick
Stop Ramp Time
.
When bit 04 = 0, a quick stop occurs.
When bit 04 = 1, if the other start conditions are fulfilled,
the frequency converter can start.
NOTICE
The selection in
parameter 8-51 Quick Stop Select
determines how bit 04 is linked with the corresponding
function of the digital inputs.
Bit 05, hold frequency output/use ramp
When bit 05 = 0, the present output frequency is
maintained, even if the reference value is modified.
When bit 05 = 1, the frequency converter can perform its
regulating function again according to the respective
reference value.
Bit 06, ramp stop/start
Normal ramp stop using the ramp times of the actual
ramp selected. In addition, if
[31] Relay 123
is selected in
parameter 5-40 Function Relay
, and if the output frequency
is 0 Hz, this bit activates output relay 01 or 04.
Bit 06 = 0 stops the frequency converter.
When bit 06 = 1, if the other start conditions are fulfilled,
the frequency converter can start.
NOTICE
The selection in
parameter 8-53 Start Select
determines
how bit 06 is linked with the corresponding function of
the digital inputs.
Bit 07, no function/reset
Reset after switching off. Acknowledges event in fault
buffer.
When bit 07 = 0, no reset occurs.
When there is a slope change of bit 07 to 1, a reset occurs
after switching off.
Bit 08, jog 1 OFF/ON
Activation of the pre-programmed speed in
parameter 8-90 Bus Jog 1 Speed
. Jog 1 is only possible if bit
04 = 0 and bits 00–03 = 1.
Bit 09, jog 2 OFF/ON
Activation of the pre-programmed speed in
parameter 8-91 Bus Jog 2 Speed
. Jog 2 is only possible if bit
04 = 0 and bits 00–03 = 1.
Control
PROFINET
14
Danfoss A/S © 04/2017 All rights reserved.
MG06G102